Instructions / Assembly

26
Installation Checklist
A. Water Heater Location
B. Water Supply
C. Gas Supply
D. Relief Valve
E. Venting
In a location where the vent system will be
within the requirements specified this manual.
Indoors and protected from freezing
temperatures.
Proper clearance from combustible surfaces
observed and water heater not installed on
carpeted floor.
Sufficient fresh air supply for proper
operation of water heater.
Air supply free of corrosive elements and
flammable vapors.
Provisions made to protect area from water
damage.
Sufficient room to service heater.
Combustible materials, such as clothing,
cleaning materials, rags, etc. clear of the base
of the heater.
Clearances of 1 in. (2.5 cm) from combustion
air inlet openings observed
Flammable vapor sensor is not blocked.
Water heater completely filled with water.
Air purged from water heater and piping.
Water connections tight and free of leaks.
Gas line equipped with shutoff valve, union
and sediment trap.
The required inlet gas pressure to the water
heater is shown on the water heater rating
plate.
Soap and water solution used to check all
connections and fittings for possible gas leak.
Gas Company inspected installation (if
required).
Temperature and Pressure Relief Valve
properly installed and discharge line run to
open drain.
Discharge line protected from freezing.
Water Heater vented separately from all other
appliances.
Blower assembly properly installed.
Proper materials and techniques used in vent
assembly.
Vent pipe properly secured to exhaust
connector of the blower assembly.
Vent system supported at required intervals.
Appropriate minimum clearances observed.
Precautions taken to prevent moisture damage
around vent termination.
Vapors from non-metallic pipe cement and
primer have dissipated prior to applying
electrical power.
F. Wiring
Correct power supply (120 V).
Electrical connections tight.
Heater properly grounded and proper polarity
observed.