Gas Valve LED Codes
CAUTION: Make certain power to water heater is “OFF” before removing protective cover FOR ANY REASON.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous
operation. VERIFY PROPER OPERATION AFTER SERVICING.
CAUTION: For your safety DO NOT attempt repair of gas piping, remote control, burners, vent connectors or other
safety devices. Refer repairs to qualified service personnel.
GAS VALVE LED STATUS/PROBLEM PROBABLE CAUSE SOLUTION
Short ash once ev-
ery four seconds
Normal Operating
Condition/ No Fault
Condition
Water Temperature setpoint has been
achieved
None required
“Heartbeat”, alter-
nates bright/dim
Calling For Heat/No
Fault Conditions
Water temperature is below setpoint and
burner is on
None required
One Flash, three
second pause
Control still operating/
Low ame signal
Pilot tube restricted or damaged
Carbon build-up on pilot's electrode
Pilot igniter wire damaged
Gas supply problems
Replace Pilot assembly
Correct gas supply
Two Flashes, three
second pause.
Sytem in Lockout/Flue
Damper Switch closed
Flue Damper improperly sealed
Flue Damper switch stuck closed
Faulty Flue Damper motor
Obstruction or debris in damper open-
ing
Inspect Flue Damper wiring and con-
nections
Replace Flue Damper Assembly
Contact a qualied service techni-
cian. See "IF YOU NEED SER-
VICE" on page 28
Three Flashes, three
second pause
System in Lockout/Flue
Damper Switch open
Flue Damper improperly installed
Flue Damper switch stuck open
Faulty Flue Damper switch
Incorrect wiring and/or connections
Faulty Flue Damper motor
Obstruction or debris in damper open-
ing
Inspect wiring and connections
Replace Flue Damper Assembly
Contact a qualied service techni-
cian. See "IF YOU NEED SER-
VICE" on page 28
Four Flashes, three
second pause
System in Lockout/
Thermal Cutoff Device
tripped
Thermal well fault in Gas Control
(Thermostat)
Gas Control (Thermostat) faulty
Tank not lled with water
Reset Gas Control (Thermostat) and
check for proper cycling of control.
Replace Gas Control (Thermostat)
Ensure tank is completely lled with
water
Five Flashes, three
second pause
System in Lockout/No
Flame Sense
Pilot and/or Main Burner valve has
failed to open
Replace the Gas Control (Thermostat)
Six-One Flashes,
three second pause
System in Lockout/
Unit failed to light
Pilot ame unstable
Pilot tube restricted or damaged
Carbon build-up on pilot's electrode
Pilot igniter wire damaged
Gas supply problem(s)
Replace Pilot assembly
Correct gas supply
Six-Two Flashes,
three second pause
System in Lockout/
Flue Damper Switch
opened
Improper Flue Damper installation
Faulty Flue Damper switch
Incorrect wiring and/or connections
Inspect Flue Damper wiring and con-
nections
Replace Flue Damper Assembly
Contact a qualied service techni-
cian. See "IF YOU NEED SER-
VICE" on page 28
Six-Three Flashes,
three second pause
System in Lockout/
Flame Lost
Combustion air supply restricted or
blocked
Pilot tube restricted or damaged
Carbon build-up on pilot's electrode
Pilot igniter wire damaged
Gas supply problem(s)
Ensure combustion air supply is not
blocked or restricted
Replace Pilot assembly
Correct gas supply