Instructions / Assembly
9
Thermal Expansion
Determine if a check valve exists in the 
inlet water line. Check with your local 
water utility company. It may have been 
installed in the cold water line as a separate 
back flow preventer, or it may be part of 
a pressure reducing valve, water meter or 
water softener. A check valve located in 
the cold water inlet line can cause what is 
referred to as a “closed water system”. A 
cold water inlet line with no check valve or 
back flow prevention device is referred to as 
an “open” water system.
As water is heated, it expands in volume and 
creates an increase in the pressure within the 
water system. This action is referred to as 
“thermal expansion”. In an “open” water 
system, expanding water which exceeds the 
capacity of the water heater flows back into 
the city main where the pressure is easily 
dissipated.
A “closed water system”, however, 
prevents the expanding water from flowing 
back into the main supply line, and the 
result of “thermal expansion” can create 
a rapid and dangerous pressure increase in 
the water heater and system piping. This 
rapid pressure increase can quickly reach 
the safety setting of the relief valve, causing 
it to operate during each heating cycle. 
Thermal expansion, and the resulting rapid, 
and repeated expansion and contraction of 
components in the water heater and piping 
system can cause premature failure of the 
relief valve, and possibly the heater itself. 
Replacing the relief valve will not correct 
the problem!
The suggested method of controlling thermal 
expansion is to install an expansion tank 
in the cold water line between the water 
heater and the check valve (see illustration 
below). The expansion tank is designed 
with an air cushion built in that compresses 
as the system pressure increases, thereby 
relieving the over pressure condition and 
eliminating the repeated operation of the 
relief valve. Other methods of controlling 
thermal expansion are also available. 
Contact your installing contractor, water 
supplier or plumbing inspector for additional 
information regarding this subject.
Typical Installation
Heat trap  
6” minimum
Heat trap  
6” minimum
Union
To gas supply
Sediment trap
Cap
Ground joint union
Drain Pan Pipe to suitable drain.
Drain 
valve
Relief valve discharge 
line to suitable open 
drain.
To cold water 
supply
6” Air gap
Draft hood
Pitch up 1/4”   
per foot
Auxiliary drain pan
Union
Anode
Manual gas shut-off
Thermostatic gas valve
Jacket door
Temperature and 
pressure relief valve
Refer to the illustration below for suggested 
typical installation. The installation of unions 
or flexible copper connectors is recommended 
on the hot and cold water connections so that 
the water heater may be easily disconnected 
for servicing if necessary. The HOT and COLD 
water connections are clearly marked and are 
3/4 in. NPT on all models. Install a shut-off 
valve in the cold water line near the water 
heater.
Water Supply Connections
IMPORTANT: DO NOT 
apply heat to the HOT or 
COLD water connections. If 
sweat connections are used, 
sweat tubing to adapter 
before fitting adapter to the 
cold water connections on 
heater. Any heat applied 
to the cold water supply 
fittings will permanently 
damage the dip tube and 
the heat traps in the hot/
cold nipples.
Shut-off valve
Shut-off 
valve
Thermal expansion 
tank (if required)
NOTICE: The National 
Fuel Gas Code (NFGC) 
mandates a manual 
gas shut-off valve: See 
(NFGC) for complete 
instructions. Local codes 
or plumbing authority 
requirements may vary 
from the instructions or 
diagrams provided and 
take precedent over these 
instructions.
Combustion Air 
Inlet Openings
Hot water outlet to 
fixtures
Water Heater Jacket
Vent connector to 
chimney










