Specification Sheet
Air
Performance Data
13PJP Series
5
Performance Data @ AHRI Standard Conditions
Model Numbers
AHRI Cooling Performance AHRI Heating Performance (70°F [21°C] Indoor)
80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Outdoor Air
47°F [8.5°C] DB/
43°F [6°C] WB
DOE High Temp.
Outdoor Air
17°F [–8.5°C] DB/
15°F [–9.5°C] WB
DOE Low Temp.
DOE
Region
IV
HSPF
Outdoor
Unit
13PJP
Indoor
Coil and/or
Air Handler
Total
Capacity
BTU/H
[kW]
Net
Sens.
BTU/H
[kW]
Net
Latent
BTU/H
[kW]
EER SEER
Snd.
Rate
dB
Indoor
CFM
[L/s]
BTU/H
[kW]
COP
BTU/H
[kW]
COP
18
RHLP-HM2417(RCSP-H*2417)
➀
17,700
[5.2]
13,500
[4.0]
4,200
[1.2]
11.00 13.00 76
600
[283]
16,400
[4.8]
3.64
8,600
[2.5]
2.08 7.70
24
RHLP-HM2417(RCSP-H*2417)
➀
23,000
[6.7]
17,800
[5.2]
5,200
[1.5]
11.00 13.00 74
775
[366]
22,200
[6.5]
3.68
13,100
[3.8]
2.48 7.70
30
RHLP-HM3617(RCSP-H*3617)
➀
28,800
[8.4]
21,500
[6.3]
7,300
[2.1]
11.00 13.00 73
1,000
[472]
27,600
[8.1]
3.76
17,400
[5.1]
2.70 7.70
36
RHLP-HM3617(RCSP-H*3617)
➀
34,800
[10.2]
26,100
[7.6]
8,700
[2.5]
11.00 13.00 75
1,175
[554]
34,600
[10.1]
3.54
21,800
[6.4]
2.58 7.70
42
RHLP-HM4821(RCSP-H*4821)
➀
40,500
[11.9]
30,300
[8.9]
10,200
[3.0]
11.00 13.00 77
1,350
[637]
39,500
[11.6]
3.72
25,000
[7.3]
2.68 7.70
48
RHLP-HM4821(RCSP-H*4821)
➀
48,500
[14.2]
36,700
[10.8]
11,800
[3.5]
11.00 13.00 77
1,550
[731]
46,000
[13.5]
3.66
29,200
[8.6]
2.66 7.70
Rev. 10/4/12
➀ Highest sales volume tested combination required by D.O.E. test procedures. [ ] Designates Metric Conversions