Air Heat Pumps 14PJM Series Rheem Value Series Heat Pumps 14PJM- Series Efficiencies up to 14.50 SEER/12.00 EER/8.50 HSPF Nominal Sizes 1.5-5 Ton [5.28 to 17.6 kW] “Proper sizing and installation of equipment is critical to achieve optimal performance. Ask your Contractor for details or visit www.energystar.gov.” • Rheem Value Series remote heat pumps offer comfort and dependability for single, multi-family and light commercial applications.
Air Table of Contents 14PJM Series TABLE OF CONTENTS Model Number Identification ............................................................................3 Accessories....................................................................................................3 Scroll Compressor ..........................................................................................3 Performance Data ......................................................................................
Air Model I.D./Accessories/Compressor 14PJM Series Model Number Identification 14 P J M 18 A 01 14.5 SEER P = HEAT PUMP VOLTAGE M = 2ND DESIGN (R-410A) NOMINAL COOLING CAPACITY CABINET 18 = 18,000 BTU/HR [5.28 kW] 24 = 24,000 BTU/HR [7.03 kW] 30 = 30,000 BTU/HR [8.79 kW] 36 = 36,000 BTU/HR [10.55 kW] 42 = 42,000 BTU/HR [12.31 kW] 48 = 48,000 BTU/HR [14.07 kW] 60 = 60,000 BTU/HR [17.
Air Performance Data 14PJM Series Performance Data @ AHRI Standard Conditions Total Capacity BTU/H [kW] AHRI Cooling Performance 80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air 95°F [35°C] DB Outdoor Air Net Net Snd. Sens. Latent EER SEER Rate BTU/H BTU/H dB [kW] [kW] Indoor CFM [L/s] AHRI Heating Performance (70°F [21°C] Indoor) Outdoor Air Outdoor Air 47°F [8.5°C] DB/ 17°F [–8.5°C] DB/ DOE 43°F [6°C] WB 15°F [–9.5°C] WB Region DOE High Temp. DOE Low Temp.
Air Performance Data 14PJM Series Performance Data @ AHRI Standard Conditions Total Capacity BTU/H [kW] AHRI Cooling Performance 80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air 95°F [35°C] DB Outdoor Air Net Net Snd. Sens. Latent EER SEER Rate BTU/H BTU/H dB [kW] [kW] Indoor CFM [L/s] AHRI Heating Performance (70°F [21°C] Indoor) Outdoor Air Outdoor Air 47°F [8.5°C] DB/ 17°F [–8.5°C] DB/ DOE 43°F [6°C] WB 15°F [–9.5°C] WB Region DOE High Temp. DOE Low Temp.
Air Performance Data 14PJM Series Performance Data @ AHRI Standard Conditions Total Capacity BTU/H [kW] AHRI Cooling Performance 80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air 95°F [35°C] DB Outdoor Air Net Net Snd. Sens. Latent EER SEER Rate BTU/H BTU/H dB [kW] [kW] Indoor CFM [L/s] AHRI Heating Performance (70°F [21°C] Indoor) Outdoor Air Outdoor Air 47°F [8.5°C] DB/ 17°F [–8.5°C] DB/ DOE 43°F [6°C] WB 15°F [–9.5°C] WB Region DOE High Temp. DOE Low Temp.
Air Performance Data 14PJM Series Performance Data @ AHRI Standard Conditions Total Capacity BTU/H [kW] AHRI Cooling Performance 80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air 95°F [35°C] DB Outdoor Air Net Net Snd. Sens. Latent EER SEER Rate BTU/H BTU/H dB [kW] [kW] Indoor CFM [L/s] AHRI Heating Performance (70°F [21°C] Indoor) Outdoor Air Outdoor Air 47°F [8.5°C] DB/ 17°F [–8.5°C] DB/ DOE 43°F [6°C] WB 15°F [–9.5°C] WB Region DOE High Temp. DOE Low Temp.
Air Performance Data 14PJM Series Performance Data @ AHRI Standard Conditions Outdoor Unit 14PJM Indoor Coil and/or Air Handler Total Capacity BTU/H [kW] AHRI Cooling Performance 80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air 95°F [35°C] DB Outdoor Air Net Net Snd. Sens. Latent EER SEER Rate BTU/H BTU/H dB [kW] [kW] Indoor CFM [L/s] AHRI Heating Performance (70°F [21°C] Indoor) Outdoor Air Outdoor Air 47°F [8.5°C] DB/ 17°F [–8.5°C] DB/ DOE 43°F [6°C] WB 15°F [–9.5°C] WB Region DOE High Temp.
Air Performance Data 14PJM Series Performance Data @ AHRI Standard Conditions Total Capacity BTU/H [kW] AHRI Cooling Performance 80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air 95°F [35°C] DB Outdoor Air Net Net Snd. Sens. Latent EER SEER Rate BTU/H BTU/H dB [kW] [kW] Model Numbers Outdoor Unit 14PJM Indoor Coil and/or Air Handler Indoor CFM [L/s] AHRI Heating Performance (70°F [21°C] Indoor) Outdoor Air Outdoor Air 47°F [8.5°C] DB/ 17°F [–8.5°C] DB/ DOE 43°F [6°C] WB 15°F [–9.
Air Performance Data 14PJM Series Performance Data @ AHRI Standard Conditions Total Capacity BTU/H [kW] AHRI Cooling Performance 80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air 95°F [35°C] DB Outdoor Air Net Net Snd. Sens. Latent EER SEER Rate BTU/H BTU/H dB [kW] [kW] Indoor CFM [L/s] AHRI Heating Performance (70°F [21°C] Indoor) Outdoor Air Outdoor Air 47°F [8.5°C] DB/ 17°F [–8.5°C] DB/ DOE 43°F [6°C] WB 15°F [–9.5°C] WB Region DOE High Temp. DOE Low Temp.
Air Performance Data 14PJM Series Performance Data @ AHRI Standard Conditions Outdoor Unit 14PJM Indoor Coil and/or Air Handler Total Capacity BTU/H [kW] AHRI Cooling Performance 80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air 95°F [35°C] DB Outdoor Air Net Net Snd. Sens. Latent EER SEER Rate BTU/H BTU/H dB [kW] [kW] Indoor CFM [L/s] AHRI Heating Performance (70°F [21°C] Indoor) Outdoor Air Outdoor Air 47°F [8.5°C] DB/ 17°F [–8.5°C] DB/ DOE 43°F [6°C] WB 15°F [–9.5°C] WB Region DOE High Temp.
Air Performance Data 14PJM Series Performance Data @ AHRI Standard Conditions Total Capacity BTU/H [kW] AHRI Cooling Performance 80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air 95°F [35°C] DB Outdoor Air Net Net Snd. Sens. Latent EER SEER Rate BTU/H BTU/H dB [kW] [kW] Indoor CFM [L/s] AHRI Heating Performance (70°F [21°C] Indoor) Outdoor Air Outdoor Air 47°F [8.5°C] DB/ 17°F [–8.5°C] DB/ DOE 43°F [6°C] WB 15°F [–9.5°C] WB Region DOE High Temp. DOE Low Temp.
Air Performance Data 14PJM Series Performance Data @ AHRI Standard Conditions Outdoor Unit 14PJM Indoor Coil and/or Air Handler Total Capacity BTU/H [kW] AHRI Cooling Performance 80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air 95°F [35°C] DB Outdoor Air Net Net Snd. Sens. Latent EER SEER Rate BTU/H BTU/H dB [kW] [kW] Indoor CFM [L/s] AHRI Heating Performance (70°F [21°C] Indoor) Outdoor Air Outdoor Air 47°F [8.5°C] DB/ 17°F [–8.5°C] DB/ DOE 43°F [6°C] WB 15°F [–9.5°C] WB Region DOE High Temp.
Air Performance Data 14PJM Series Performance Data @ AHRI Standard Conditions Outdoor Unit 14PJM Indoor Coil and/or Air Handler Total Capacity BTU/H [kW] AHRI Cooling Performance 80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air 95°F [35°C] DB Outdoor Air Net Net Snd. Sens. Latent EER SEER Rate BTU/H BTU/H dB [kW] [kW] Indoor CFM [L/s] AHRI Heating Performance (70°F [21°C] Indoor) Outdoor Air Outdoor Air 47°F [8.5°C] DB/ 17°F [–8.5°C] DB/ DOE 43°F [6°C] WB 15°F [–9.5°C] WB Region DOE High Temp.
Air Performance Data 14PJM Series Performance Data @ AHRI Standard Conditions Total Capacity BTU/H [kW] AHRI Cooling Performance 80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air 95°F [35°C] DB Outdoor Air Net Net Snd. Sens. Latent EER SEER Rate BTU/H BTU/H dB [kW] [kW] Indoor CFM [L/s] AHRI Heating Performance (70°F [21°C] Indoor) Outdoor Air Outdoor Air 47°F [8.5°C] DB/ 17°F [–8.5°C] DB/ DOE 43°F [6°C] WB 15°F [–9.5°C] WB Region DOE High Temp. DOE Low Temp.
Air Performance Data 14PJM Series Performance Data @ AHRI Standard Conditions Total Capacity BTU/H [kW] AHRI Cooling Performance 80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air 95°F [35°C] DB Outdoor Air Net Net Snd. Sens. Latent EER SEER Rate BTU/H BTU/H dB [kW] [kW] Indoor CFM [L/s] AHRI Heating Performance (70°F [21°C] Indoor) Outdoor Air Outdoor Air 47°F [8.5°C] DB/ 17°F [–8.5°C] DB/ DOE 43°F [6°C] WB 15°F [–9.5°C] WB Region DOE High Temp. DOE Low Temp.
Air Electrical and Physical Data 14PJM Series Electrical and Physical Data ELECTRICAL PHYSICAL Model Compressor Fuse or HACR Fan Motor Minimum Outdoor Coil Phase Number Circuit Breaker Rated Load Locked Rotor Full Load Circuit Frequency (Hz) 14PJM Amperes Amperes Ampacity Minimum Maximum Face Area No. Voltage (Volts) Amperes (FLA) Amperes Amperes Amperes Sq. Ft. [m2] Rows CFM [L/s] (RLA) (LRA) Refrig. Per Circuit Oz. [g] Weight Net Lbs. [kg] Shipping Lbs. [kg] Rev.
Air Unit Dimensions 14PJM Series Unit Dimensions Model No. 14PJM Unit Dimensions Width “W” Inches [mm] Length “L” Inches [mm] Height “H”* Inches [mm] 275/8 [701.6] 315/8 [803.2] 275/8 [701.6] 315/8 [803.2] 261/4 [666.7] 273/8 [695.3] 36, 42, 48, 60 315/8 [803.2] *Dimensions includes Baserails and/or basepan. 315/8 [803.
Air Refrigerant Line Size Information 14PJM Series Heat Pump Refrigerant Line Size Information System Capacity Line Size Connection Size (Inch I.D.) [mm] 11/2 Ton 3/8" [9.53] 3/8" [9.53] 2 Ton 3/8" [9.53] 21/2 Ton [6.35] 25 [7.62] Liquid Line Sizing (R410A) Outdoor Unit Above or Below Indoor Coil (Heat Pumps Only) Total Equivalent Length—Feet [m] 50 [15.24] 75 [22.86] 100 [30.48] 125 [38.10] Maximum Vertical Separation—Feet [m] 40 [12.19] 25 [7.62] 9 [2.74] N/A 5/16 [7.94] 25 [7.62] 50 [15.
Air Limited Warranty 14PJM Series GENERAL TERMS OF LIMITED WARRANTY* Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable period stated, in accordance with the terms of the limited warranty. *For complete details of the Limited and Conditional Warranties, including applicable terms and conditions, contact your local contractor or the Manufacturer for a copy of the product warranty certificate.
Air Notes 14PJM Series 21
Air 22 Notes 14PJM Series
Air Notes 14PJM Series 23
The new degree of comfort.™ In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice. Rheem Heating, Cooling & Water Heating • P.O. Box 17010 Fort Smith, Arkansas 72917 • www.rheem.com Rheem Canada Ltd./Ltée • 125 Edgeware Road, Unit 1 Brampton, Ontario • L6Y 0P5 PRINTED IN U.S.A 02/13 QG FORM NO. P11-803 REV.