SPECIFICATIONS
Model
850330 850360
Max Water Supply Pressure With ECV 960 960
(kPa) Without ECV 1120 1120
Min Gas Supply Pressure - Natural Gas (kPa) 1.13 1.13
Minimum Gas Supply Pressure -LP Gas (kPa) 2.75 2.75
Maximum Gas Supply Pressure (kPa) 3.5 3.5
Maximum Thermostat Setting (ºC) 66 66
ECO Cut Out Temperature (ºC) 82+/-3 82+/- 3
Storage Capacity (litres) 130 160
Hourly Recovery (45°C rise) 200 200
Anodes Quantity 2 2
Length (mm) 1153 1400
Flue Baffle Blades 20 22
Length (mm) 1214 1315
Water Connections Diameter RP¾/20 RP¾/20
T&PR Valve Diameter RP½/15 RP½/15
Rating (kPa) 1400 1400
Gas Connection RP½/15 RP½/15
Pilot injector (mm) LP gas 0.18 0.18
Natural gas 0.27 0.27
Gas Control Std pilot LP gas only LP gas only
Regulated Pilot Natural gas Natural gas
Burner Injector (mm) LP gas 1.60 1.60
Natural Gas 2.90 2.90
Thermal Input (MJ) 42 42
BALANCED FLUE PRINCIPAL
In practice it is almost impossible to achieve exact
balance between the pressures on the air inlet and flue
outlet of a balanced flue terminal. In order to avoid the
possibility of reverse fluing the flue terminal design is
always biased to provide slightly higher pressure on the
air inlet.
The flue terminal is designed and tested to operate with
winds directed at the side or front of the water heater. If
the wind comes from the behind the water heater, the
operation of the flue terminal is unpredictable and may
result in problems such as flame roll out from the
combustion chamber, sooting of the primary flue and
stainless steel super flue and/or pilot outage.
For this reason the water heater must be installed
against an external wall.