Specifications

Stellar Service Instructions REV: D
Date of Issue: 14/09/2007
This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
17
FAULT FINDING – TESTS 1-4
TEST 1 TEST 2
Using a multimeter set on the x1 resistance scale,
measure across the terminals of the interrupter block on
the gas control. The reading should be 0 ohms (dead
short).
Disconnect the thermocouple from the gas control and
using a multimeter set on the DC millivolt scale measure
the voltage being generated by the thermocouple.
Normal voltage should be approximately 20 millivolts.
Note: It will be necessary to light the pilot and manually
hold the gas control knob down during this test.
TEST 3 TEST 4
With the thermocouple connected to the gas control and
using a multimeter set on the DC millivolt scale,
measure the voltage between the lower terminal of the
interrupter block and the thermocouple sheath. The
reading should be approximately 14 millivolts.
Using a multimeter set on the x1 resistance scale,
measure the resistance between the wiring terminal and
the electrode tip (ensure the tip is clean). Resistance
should be 0 ohms (dead short).