Specification Sheet

Air
Airflow Performance Data
RHLP Series
9
External Static Pressure—Inches W.C. [kPa]
PSC CFM [L/s] Air Delivery/RPM/Watts—115/208/240 Volts
RPM 660
Blower Size/
Motor
HP [W]
# of Speed
-4821
with 20 kW
Heater
698
Tonnage
Application
734
Manufacturer
Recommended
Air-Flow Range
(Min/Max) CFM
Motor
Speed
762 795
Watts 297 311 326 340 353
11x11
3/4 HP [559]
5 Speed
3
CFM 1732 [817] 1683 [794] 1630 [769]
RPM
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
840 872 899
Model
No.
RHLP
-4824
No Heater
-4824
with 25 kW
Heater
RPM
4 Ton
1545/1732 CFM
[729/817 L/s]
2
CFM 1748 [825] 1669 [788] 1639 [773] 1599 [755] 1545 [729]
Watts 448 467 480
RPM 680 736
-4821
No Heater
760 790 820
831
875 919 954
Watts 305 330 341 350 361
11x11
3/4 HP [559]
5 Speed
3
CFM
989
1692 [798] 1643 [775] 1590 [750]
RPM 865 890 1014
Watts 277 295 313 319 325
4 Ton
1505/1692 CFM
[710/798 L/s]
2
CFM 1708 [806] 1629 [769] 1599 [755] 1559 [736] 1505 [710]
Watts 460 470 481
10x10
3/4 HP [559]
5 Speed
3
CFM 1333 [629] 1300 [613] 1267 [598]
RPM
RPM 781 825 867 905 949
Watts 257 271 303 307 315
10x10
3/4 HP [559]
5 Speed
3
CFM 1447 [683] 1433 [676] 1402 [662]
RPM 987 1034 1065
1011 1046 1080
3.5 Ton
1297/1333 CFM
[612/629 L/s]
3.5 Ton
1337/1447 CFM
[631/683 L/s]
2
CFM 1473 [695] 1442 [681] 1401 [661] 1373 [648] 1337 [631]
Watts
394 406 405
2
CFM 1433 [676] 1402 [662] 1361 [642] 1333 [629] 1297 [612]
Watts
350 364 377
-4821
No Heater
RPM 853 893 934 968 1015
Watts 351 387 401 406 422
10x10
3/4 HP [559]
5 Speed
5
CFM 1654 [781] 1624 [766] 1563 [738]
RPM 1036 1078 1095
4 Ton
1535/1654 CFM
[724/781 L/s]
4
CFM 1665 [786] 1631 [770] 1601 [756] 1572 [742] 1535 [724]
Watts
500 513 523
-4821
with 25 kW
Heater
RPM 894 932 970 1020 1052
Watts 389 400 410 430 450
10x10
3/4 HP [559]
2 Speed
5
CFM 1614 [762] 1584 [748] 1523 [719]
RPM 1085 1090 1105
4 Ton
1495/1614 CFM
[706/762 L/s]
4
CFM 1625 [767] 1591 [751] 1561 [737] 1532 [723] 1495 [706]
Watts 514 520 530
Motor
Speed
From
Factory
3
3
5
5
5
5
115V/208V/240V/460V Airflow Performance Data—RHLP (X-13 (ECM) Motor) (con’t.)
Notes: X-13 (ECM) motor speed changes.
All X-13 (ECM) motors have 5 speed tabs. Speed tab 1 is for continuous fan. Speed tab 2 (low static) and Speed tab 3 (high static) are for lower tonnage. Speed tab 4
(low static) and Speed tab 5 (high static) are for higher tonnage.
X-13 (ECM) air handlers are always shipped from factory at Speed tab 5, except for -4824, which is set at Speed tab 3. For instance, RHLP-HM2417JA is always
shipped at high static 2-ton airflow (Speed tab 5). To change to 1.5-ton airflow, move the blue wire to Speed tab 2 or 3 on the X-13 (ECM) motor.
The low static Speed tab 2 (lower tonnage) and 4 (higher tonnage) are used for external static below 0.5" WC. The high static Speed tab 3 (lower tonnage) and 5
(higher tonnage) are used for external static exceeding 0.5" WC. Move the blue wire to the appropriate Speed tab as required by the application needs.
The airflow for continuous fan (Speed tab 1) is always set at 50% of the Speed tab 4.
The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed.
Approximate Airflow = Airflow without heater – (Airflow without heater – Airflow with maximum heater) x (N kW/maximum heater kW)
[ ] Designates Metric Conversions