Specification Sheet
Air
Electrical Data
RHLP Series
10
Electrical Data – Blower Motor Only – No Electric Heat
Model
RHLP
Voltage
Application
Phase*
Hertz HP [W] RPM Speeds
Circuit
Amps.
Minimum
Circuit
Ampacity
Maximum
Circuit
Protector
3617 1/2 [373] 300-1100 4 2.7 4.0 15
2417
208/240 1 & 3 60
1/3 [249] 300-1100 4 1.6 2.0 15
4821/4824 3/4 [559] 300-1100 4 3.8 5.0 15
3617 1/2 [373] 300-1100 4 6.8 9.0 15
2417
115 1 60
1/3 [249] 300-1100 4 4.8 6.0 15
4821/4824 3/4 [559] 300-1100 4 8.4 11.0 15
* Blower motors are all single phase motors.
[ ] Designates Metric Conversions