Specification Sheet

Air
Airflow Performance Data
RHSL Series
8
External Static Pressure—Inches W.C. [kPa]
PSC CFM [L/s] Air Delivery/RPM/Watts—240 Volts
RPM 571
Blower Size/
Motor
HP [W]
# of Speed
626
Motor
Speed
from
Factory
687
Manufacturer
Recommended
Air-Flow Range
(Min/Max) CFM
Motor
Speed
736 791
Watts 171 162 157 152 146
10x6
1/5 HP [149]
2 Speed
High
CFM 661 [312] 612 [289] 564 [266]
RPM
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
837 878
RPM 541 596 657 706 761
915
Watts 180 171 166 161 109
10x6
1/5 HP [149]
2 Speed
High
240V
487/661 CFM
[230/312 L/s]
High
CFM 711 [336] 662 [312] 614 [290]
Low
CFM 638 [301] 607 [286] 565 [267] 530 [250]
RPM 812 853 890
487 [230]
Watts 232 216 199
RPM 616 667 715 770 808
Watts 239 230 221 206 205
10x6
1/5 HP [149]
2 Speed
High
CFM 888 [419] 828 [391] 774 [365]
RPM 875 908 958
High
240V
647/888 CFM
[305/419 L/s]
Low
CFM 817 [386] 779 [368] 757 [357] 693 [327] 647 [305]
Watts 331 313 301
RPM 646 697 745 800 838
Watts 230 221 212 197 187
10x6
1/5 HP [149]
2 Speed
High
CFM 838 [395] 778 [367] 724 [342]
RPM 900 933 983
High
240V
617/838 CFM
[291/395 L/s]
Low
CFM 787 [371] 749 [353] 727 [343] 663 [313] 617 [291]
Watts
320 302 290
RPM 700 754 794 633 870
Watts 344 313 302 309 288
10x8
1/4 HP [186]
2 Speed
High
CFM 1004 [474] 951 [449] 883 [417]
RPM
High
240V
924
517/711 CFM
[244/336 L/s]
Low
CFM 668 [315] 637 [301] 595 [281] 560 [264] 517 [244]
953 975
Watts 243 227 210
High
240V
864/1004 CFM
[408/474 L/s]
Low
CFM 1022 [482] 987 [466] 940 [444] 903 [426] 864 [408]
Watts
364 352 344
RPM 750 804 844 883 920
Watts 324 293 282 274 268
10x8
1/4 HP [186]
2 Speed
High
CFM 904 [427] 851 [402] 783 [370]
RPM 949 978 1000
High
240V
814/904 CFM
[384/427 L/s]
Low
CFM 972 [459] 937 [442] 890 [420] 853 [403] 814 [384]
Watts
334 322 314
Model
No.
RHSL
-1817
with 13 kW
Heater
-2417
No Heater
-2417
with 13 kW
Heater
-1817
No Heater
-3017
No Heater
-3017
with 18 kW
Heater
-3617/-3621
No Heater
RPM 788 833 872 909 951
Watts 466 462 427 406 395
10x8
1/3 HP [249]
2 Speed
High
CFM 1248 [589] 1194 [563] 1133 [535]
RPM 1008 1028 1042
High
240V
1104/1248 CFM
[521/589 L/s]
Low
CFM 1229 [580] 1201 [567] 1170 [552] 1141 [538] 1104 [521]
Watts 488 475 454
Notes: All 208/240V PSC motors have voltage taps for 208 and 240 volts.
All 208/240V PSC motors are shipped on high speed and 240 volts.
• If the application external static is less than 0.5" WC, adjust the motor speed to the low static speed as described below:
• Unplug the black motor wire off the relay on the control board and plug in the red motor wire.
• Replace the cap on the black motor wire.
Voltage change (208/240V motors):
• Move the orange lead to transformer 208V tap from 240V tap. Replace the wire cap on 240V tap.
• Unplug the purple motor wire off the transformer and plug in the yellow motor wire.
• Replace the cap on the purple motor wire.
The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
The following formula can be used to calculate the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed.
Approximate Airflow = Airflow without heater - (Airflow without heater - Airflow with maximum heater) x (N kW/maximum heater kW)
[ ] Designates Metric Conversions
240V Airflow Performance Data—RHSL (PSC Motor)