Specification Sheet
Air
Electrical Data
RHSL Series
14
Electrical Data – With Electric Heat (Cont.)
Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the following table is recommended for all
auxiliary heating requirements.
Air Handler
Model
RHSL
Heater Model No.
Heater kW
(208/240V)
(480V)
PH/HZ
No. Elements
kW Per
Type Supply
Circuit Single
Circuit Multiple
Circuit
Amps.
Motor
Ampacity
Minimum
Circuit
Ampacity
Maximum
Circuit
Protection
3621
RXBH-1724A18J
4.3/5.7 1/60 1 - 5.68 MULTIPLE CKT 1 20.5/23.6 2.5 29/33 30/35
8.7/11.3 1/60 2 - 5.86 MULTIPLE CKT 2
41.1/47.2 0.0 52/59 60/60
RXBH-1724A07C 5.4/7.2 3/60 3 - 2.4 SINGLE
15.0/17.3 2.5 22/25 25/25
RXBH-1724A10C 7.2/9.6 3/60 3 - 3.2 SINGLE
20.0/23.1 2.5 29/32 30/35
RXBH-1724A13C 9.4/12.5 3/60 3-4.17 SINGLE
26.1/30.1 2.5 36/41 40/45
RXBH-1724A15C 10.8/14.4 3/60 3 - 4.8 SINGLE
30.0/34.6 2.5 41/47 45/50
RXBH-1724A18C 12.8/17.0 3/60 3-5.68 SINGLE
35.5/41.0 2.5 48.55 50/60
RXBH-17A07D 7.2 3/60 2-3.6 SINGLE
8.7 1.4 13 15
RXBH-17A10D 9.6 3/60 3-3.2 SINGLE
11.6 1.4 17 20
RXBH-17A15D 14.4 3/60 3-4.8 SINGLE
17.3 1.4 24 25
RXBH-17A18D 17 3/60 3-5.68 SINGLE
20.4 1.4 28 30
4221/4821
4824
RXBH-1724?05J 3.6/4.8 1/60 1 - 4.8 SINGLE
17.3/20.0 5.2 29/32 30/35
RXBH-1724?07J 5.4/7.2 1/60 2 - 3.6 SINGLE
26.0/30.0 5.2 39/44 40/45
RXBH-1724?10J 7.2/9.6 1/60 2 - 4.8 SINGLE
34.6/40.0 5.2 50/57 50/60
RXBH-1724A15J 10.8/14.4 1/60 3-4.8 SINGLE
51.9/60.0 5.2 72/82 80/90
RXBH-1724A15J
3.6/4.8 1/60 1 - 4.8 MULTIPLE CKT 1
17.3/20.0 5.2 29/32 30/35
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
RXBH-1724A18J 12.8/17 1/60 3-5.68 SINGLE
61.6/70.8 5.2 84/95 90/100
RXBH-1724A18J
4.3/5.7 1/60 1 - 5.68 MULTIPLE CKT 1
20.5/23.6 5.2 33/36 35/40
8.7/11.3 1/60 2 - 5.86 MULTIPLE CKT 2
41.1/47.2 0.0 52/59 60/60
RXBH-24A20J 14.4/19.2 1/60 4-4.8 SINGLE
69.2/80 5.2 93/107 100/110
RXBH-24A20J
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 1
34.6/40.0 5.2 50/57 50/60
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
RXBH-24A25J (4-ton only) 18.0/24.0 1/60 6-4.0 SINGLE
86.4/99.9 5.2 115/132 125/150
RXBH-24A25J
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 1
28.8/33.3 5.2 43/49 45/50
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 2
28.8/33.3 0.0 36/42 40/45
6.0/8.0 1/60 2-4.0 MULTPLE CKT 3
28.8/33.3 0.0 36/42 40/45
RXBH-1724A07C 5.4/7.2 3/60 3 - 2.4 SINGLE
15.0/17.3 5.2 26/29 30/30
RXBH-1724A10C 7.2/9.6 3/60 3 - 3.2 SINGLE
20.0/23.1 5.2 32/36 35/40
RXBH-1724A15C 10.8/14.4 3/60 3 - 4.8 SINGLE
30.0/34.6 5.2 44/50 45/50
RXBH-1724A18C 12.8/17.0 3/60 3-2.84 SINGLE
35.6/41.0 5.2 51/58 60/60
RXBH-1724A18C
4.3/5.7 3/60 3 - 2.84 MULTIPLE CKT 1
17.8/20.5 5.2 29/33 30/35
8.7/11.3 3/60 3 - 2.84 MULTIPLE CKT 2
17.8/20.5 0.0 23/26 25/30
RXBH-24A20C 7.2-9.6 3/60 3-3.2 SINGLE
40.0/46.2 5.2 57/65 60/70
RXBH-24A20C
7.2/9.6 3/60 3 - 3.2 MULTIPLE CKT 1
20.0/23.1 5.2 32/36 35/40
7.2/9.6 3/60 3 - 3.2 MULTIPLE CKT 2
20.0/23.1 0.0 25/29 25/30
RXBH-24A25C (4-ton only) 18.0/24.0 3/60 6-4.0 SINGLE
50.0/57.8 5.2 69/79 70/80
RXBH-24A25C (4-ton only)
9.0/12.0 3/60 3-4.0 MULTIPLE CKT 1
25.0/28.9 5.2 38/43 40/45
9.0/12.0 3/60 3-4.0 MULTIPLE CKT 2
25.0/28.9 0.0 32/37 35/40
RXBH-24A07D 7.2 3/60 2-3.6 SINGLE
8.7 2.2 14 15
RXBH-24A10D 9.6 3/60 3-3.2 SINGLE
11.6 2.2 18 20
RXBH-24A15D 14.4 3/60 3-4.8 SINGLE
17.3 2.2 25 25
• Supply circuit protective devices may be fuses or “HACR” type circuit breakers. 
• Largest motor load is included in single circuit and multiple circuit 1.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• J Voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3-phase power to the air handler terminal block
without the heater, bring only two leads to the terminal block cap, insulate and fully secure the third lead.
[    ] Designates Metric Conversions