Installation guide
Humidification System 
 7 69-2307—01
M24896A
Funnel or floor drain. Refer to governing 
codes for drain pipe size and maximum 
temperature requirements.
6 in.
8 in.
Most operation problems are caused 
by improper hose installation. Always 
ensure an uphill flow when installing 
the remote hose, and avoid kinks, 
sharp turns, or low spots that could 
restrict the flow of steam into the 
injection nozzle or condensation back 
into the humidifier.
If the remote hose cannot be installed 
with an upward pitch of 2 in./ft., a 
wetted drip tee must be installed. 
Failure to do so can result in back 
pressure on the humidifier, which can 
lead to duct nozzle water spitting or 
leaking gasket. Remote hose must be 
supported to prevent sagging or low 
spots.
1
Choose a location for the humidifier and the 
remote duct nozzle (see remote installs on 
page 8).
It should have access for:
• Remotehoseinstallation.Steamhose
must be installed with 2 in./ft. pitch on a 
continuous uphill slope.
• Drain.Allowacontinuousdownslopetothe
drain.
• Coldwaterline.
• Electricalcircuitratedtoyourhumidifier
(see circuit ratings on page 10).
RemoTe mounT InsTallaTIon
Use for mounting to a location other than the supply duct.
Maximum 3 ft.
2 in./ft. uphill
1/2 in. 
minimum 
diameter
When remote mounting, also follow these critical 
steps in sizing the proper humidifier:
The 6-gallon model can be remotely mounted up to 
15 feet if insulating the steam distribution tube
The 9- and 12-gallon models can be remotely mount-
ed up to 20 feet.
Ensureatleast2in.perfootslopeifinstallingthe
remote hose horizontally.
duCT mounT InsTallaTIon
Water in 
elbow