Installation guide
Humidification System 
 19 69-2307—01
The humidifier has internal system diagnostics that monitor system operation, maintenance sched-
ules, and faults. If a system fault is detected, the system will attempt to recover itself up to five 
timesina24hourperiod.Ifunabletorecoverinthattime,theredCallServiceLEDlightwillacti-
vate.
If the humidifier Call Service light is red, a system fault has occurred from which the humidifier 
can not recover by itself. The table below shows the possible faults, along with steps to fix the 
humidifier.
IftheredCallServiceLEDlightison,press/releasetheRESETbutton.TheredCallServiceLED
light will begin blinking in a series that indicates what fault occurred. Refer to the table below 
for the fault signified by the number of blinks that occur. To clear the fault, press and hold the 
RESETbuttonfor5seconds.
Press/holdtheEMPTYbuttontocleartheServiceTimerlight(i.e.thePressEmptybutton).
Press/releasetheEMPTYbuttontodrainthetank.
No. of 
Red 
Light 
Blinks
Fault Description Auto-
Recoverable?
Steps to Fix 
To be Performed by Professional HVAC Technician Only
1 Water/Heater temper-
ature sensor failed.
Yes,systemwill
return to “Ready” 
if fault no longer 
exists in 1 hour.
• Unplugthehumidifierandremovecover.
• Checkwatersensorconnectiontoelectronicboard.
• Reattachcoverandplugthehumidifierin.
• Iffaultreappears,followthecleaningstepsonpages23–25.
• ReassembletankandpresstheRESETbutton.
• Iffaultreturns,replacewithapplicablewattageheating
element.
2 Water sensors failed. Yes,systemwill
return to “Ready” 
if fault no longer 
exists in 1 hour. 
Will attempt to 
reset itself 5 times 
in 24 hours. 
• Unplugthehumidifierandremovecover.
•
Disconnect water level sensor wiring, remove screen and 
lift snap-hinge clamp. 
Remove water sensor assembly.
•Cleanwatersensorprobesusingwarmsoapywatersothat
the metal is exposed.
•Reassemblethesensorassemblyintheunit,reattachand
secure cover.
•PlugunitbackinandpresstheRESETbutton.
•Iffaultreappears,replacesensorassembly.
3 Failure to fill tank 
with water.
Yes,systemwill
return to “Ready” 
if fault no longer 
exists in 1 hour.
•Ensureinletwaterison.
•Checkforleaksaroundthetanksealandsolenoid.
•Turnoffwatersupplyandreplacein-linewaterfilter.
•Press/holdRESETbuttonuntiltheredCallServicelight
turns off.
•Iftankstillfailstofill,presstheEMPTYbutton(ifunitfailsto
drain, unplug unit and make sure water in tank is cool).
• Followtankcleaninginstructionsonpage23.Ensureyou
have a firm grip of the tank prior to releasing the tank, 
especially if water is present.
• Clearanyexcessdebrisfromthetank’sbottomorificetothe
solenoid.
• Reassembletankandplugunitbackin.PresstheRESET
button.
• Ifwaterstillfailstoflushintothetank,replacethesolenoid
valve.
M24901
A
B
TRoubleshooTIngdIP sWITCh seleCTIon