Specifications
24
[ ] Designates Metric Conversions
NOTES:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor
heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in
accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.
4. Standard 3/4” PVC P-Trap provided.
GENERAL DATA - RSPM
NOMINAL SIZES 2-5 TONS [7-17.6 kW]
Model RSPM - Series A048CK A048JK
C
ooling performance
1
Gross Cooling Capacity Btu [kW] 49,000 [14.36] 49,000 [14.36]
EER, SEER
2
12.6/14 12.6/14
Nominal CFM/ARI Rated CFM [L/s] 1600/1600 [755/755] 1600/1600 [755/755]
A
RI Net Cooling Capacity Btu [kW] 47,000 [13.77] 47,000 [13.77]
N
et Sensible Capacity Btu [kW] 36,400 [10.67] 36,400 [10.67]
N
et Latent Capacity Btu [kW] 10,600 [3.11] 10,600 [3.11]
N
et System Power kW 3.61 3.61
C
ompressor
No/Type 1/Copeland Scroll 1/Copeland Scroll
Outdoor Sound Rating (dB)
5
78 78
O
utdoor Coil - Fin Type Louvered Louvered
Tube Type Rifled Rifled
Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 16.54 [1.54] 16.54 [1.54]
Rows / FPI [FPcm] 1 / 22 [9] 1 / 22 [9]
Indoor Coil - Fin Type Louvered Louvered
Tube Type Rifled Rifled
Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5]
F
ace Area sq. ft. [sq. m] 5.78 [0.54] 5.78 [0.54]
R
ows / FPI [FPcm] 3 / 13 [5] 3 / 13 [5]
R
efrigerant Control TX Valves TX Valves
Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4]
O
utdoor Fan - Type Propeller Propeller
N
o. Used/Diameter in. [mm] 1/24 [609.6] 1/24 [609.6]
Drive Type/No. Speeds Direct/1 Direct/1
CFM [L/s] 4200 [1982] 4200 [1982]
No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP
Motor RPM 1075 1075
Indoor Fan - Type FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/11x9 [279.4x228.6] 1/11x9 [279.4x228.6]
Drive Type/No. Speeds Direct/2 Direct/2
No. Motors 11
Motor HP 3/4 3/4
Motor RPM 1050 1050
Motor Frame Size 48 48
Filter - Type Field Supplied Field Supplied
Furnished No No
(NO.) Size Recommended in. [mm x mm x mm] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610]
Refrigerant Charge Oz. [g] 114 [3232] 114 [3232]
Weights
Net Weight lbs. [kg] 349 [158] 349 [158]
Ship Weight lbs. [kg] 375 [170] 375 [170]