PACKAGE AIR CONDITIONERS User Manual

1. Horsepower Per Compressor.
2. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps.
Copper Wire Size—AWG (1% Voltage Drop)
Notes: 1. Wire size based on 60°C. type copper conductors below 100 ampacity. 2. Wire size based on 75°C. type copper conductors for 100 ampacity and above.
[ ] Designates Metric Conversions
SUPPLY WIRE
LENGTH-FEET
300 4 3 2 2 1 1/0 1/0 2/0 2/0 3/0 3/0 3/0 4/0 4/0 4/0 4/0 250 250 250 250 300 300 300
250 4 4 3 3 2 1 1 1/0 1/0 2/0 2/0 2/0 3/0 3/0 3/0 4/0 4/0 4/0 4/0 4/0 250 250 250
200 6 4 4 4 3 2 2 1 1 1/0 1/0 1/0 2/0 2/0 2/0 3/0 3/0 3/0 3/0 3/0 4/0 4/0 4/0
150 8 6 6 4 4 4 3 3 2 2 1 1 1/0 1/0 1/0 1/0 2/0 2/0 2/0 2/0 2/0 3/0 3/0
CIRCUIT AMPACITY
100 10 8 8 6 6 6 4 4 4 3 3 2 2 2 1 1 1 1 1 1/0 1/0 1/0 1/0
50 14 12 10 10 8 8 6 6 6 4 4 4 3 3 3 2 2 2 2 2 1 1 1
15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125
16
ELECTRICAL DATA—RSNA-B SERIES