Specification Sheet

Physical Data
Model No.# RP1418 RP1424 RP1430 RP1436 RP1442 RP1448 RP1460
Nominal Tonnage 1.5 2.0 2.5 3.0 3.5 4.0 5.0
Valve Connections
Liquid Line O.D. – in. 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Suction Line O.D. – in. 3/4 3/4 3/4 3/4 7/8 7/8 7/8
Refrigerant (R410A) furnished oz.¹ 103 100.8 118 123 167 155 244
Compressor Type Scroll
Outdoor Coil
Net face area – Outer Coil 9.1 9.1 11.1 14.9 14.8 19.8 24.2
Net face area – Inner Coil
Tube diameter – in. 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Number of rows 1 1 1 1 1 1 1
Fins per inch 20 20 20 20 20 20 20
Outdoor Fan
Diameter – in. 20 20 20 24 24 24 26
Number of blades 2 2 3 3 2 3 3
Motor hp 1/8 1/8 1/8 1/6 1/6 1/5 1/5
CFM 2410 2410 2535 3335 2945 4055 4780
RPM 1077 1077 1077 825 850 825 850
watts 154 156 142 173 161 228 279
Shipping weight – lbs. 156 151 162 178 208 234 269
Operating weight – lbs. 149 144 155 171 201 227 262
Electrical Data
Line Voltage Data (Volts-Phase-Hz) 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Maximum overcurrent protection (amps)² 20 25 30 35 40 45 50
Minimum circuit ampacity³ 12 17 19 20 24 26 31
Compressor
Rated load amps 9 12.8 14.1 15.4 17.9 19.6 23.7
Locked rotor amps 48 58.3 73 83.9 112 130 152.5
Condenser Fan Motor
Full load amps 0.7 0.7 0.7 0.6 0.9 1.2 1
Locked rotor amps 1.2 1.2 1.2 1.5 1.2 2 2.4
Line Voltage Data (Volts-Phase-Hz) 208/230-3-60 208/230-3-60 208/230-3-60 208/230-3-60
Maximum overcurrent protection (amps)² 20 30 30 35
Minimum circuit ampacity³ 14 18 19 21
Compressor
Rated load amps 10.4 13.5 13.7 15.9
Locked rotor amps 73 88 83.1 110
Condenser Fan Motor
Full load amps 0.6 0.9 1.2 1
Locked rotor amps 1.5 1.2 2 2.3
Line Voltage Data (Volts-Phase-Hz) 480-3-60 480-3-60 480-3-60 480-3-60
Maximum overcurrent protection (amps)² TBD TBD TBD TBD
Minimum circuit ampacity³ TBD TBD TBD TBD
Compressor
Rated load amps TBD TBD TBD TBD
Locked rotor amps TBD TBD TBD TBD
Condenser Fan Motor
Full load amps TBD TBD TBD TBD
Locked rotor amps TBD TBD TBD TBD
¹Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the installation instructions for information about set length and additional
refrigerant charge required.
²HACR type circuit breaker of fuse.
³Refer to National Electrical Code manual to determine wire, fuse and disconnect size requirements.
Air
Physical Data/Electrical Data
RP14 Series
8