Specification Sheet
Physical Data
Model No.# RP1418 RP1424 RP1430 RP1436 RP1442 RP1448 RP1460
Nominal Tonnage 1.5 2.0 2.5 3.0 3.5 4.0 5.0
Valve Connections
Liquid Line O.D. – in. 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Suction Line O.D. – in. 3/4 3/4 3/4 3/4 7/8 7/8 7/8
Refrigerant (R410A) furnished oz.¹ 103 100.8 118 123 167 155 244
Compressor Type Scroll
Outdoor Coil
Net face area – Outer Coil 9.1 9.1 11.1 14.9 14.8 19.8 24.2
Net face area – Inner Coil — — — — — — —
Tube diameter – in. 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Number of rows 1 1 1 1 1 1 1
Fins per inch 20 20 20 20 20 20 20
Outdoor Fan
Diameter – in. 20 20 20 24 24 24 26
Number of blades 2 2 3 3 2 3 3
Motor hp 1/8 1/8 1/8 1/6 1/6 1/5 1/5
CFM 2410 2410 2535 3335 2945 4055 4780
RPM 1077 1077 1077 825 850 825 850
watts 154 156 142 173 161 228 279
Shipping weight – lbs. 156 151 162 178 208 234 269
Operating weight – lbs. 149 144 155 171 201 227 262
Electrical Data
Line Voltage Data (Volts-Phase-Hz) 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Maximum overcurrent protection (amps)² 20 25 30 35 40 45 50
Minimum circuit ampacity³ 12 17 19 20 24 26 31
Compressor
Rated load amps 9 12.8 14.1 15.4 17.9 19.6 23.7
Locked rotor amps 48 58.3 73 83.9 112 130 152.5
Condenser Fan Motor
Full load amps 0.7 0.7 0.7 0.6 0.9 1.2 1
Locked rotor amps 1.2 1.2 1.2 1.5 1.2 2 2.4
Line Voltage Data (Volts-Phase-Hz) — — — 208/230-3-60 208/230-3-60 208/230-3-60 208/230-3-60
Maximum overcurrent protection (amps)² — — — 20 30 30 35
Minimum circuit ampacity³ — — — 14 18 19 21
Compressor
Rated load amps — — — 10.4 13.5 13.7 15.9
Locked rotor amps — — — 73 88 83.1 110
Condenser Fan Motor
Full load amps — — — 0.6 0.9 1.2 1
Locked rotor amps — — — 1.5 1.2 2 2.3
Line Voltage Data (Volts-Phase-Hz) — — — 480-3-60 480-3-60 480-3-60 480-3-60
Maximum overcurrent protection (amps)² — — — TBD TBD TBD TBD
Minimum circuit ampacity³ — — — TBD TBD TBD TBD
Compressor
Rated load amps — — — TBD TBD TBD TBD
Locked rotor amps — — — TBD TBD TBD TBD
Condenser Fan Motor
Full load amps — — — TBD TBD TBD TBD
Locked rotor amps — — — TBD TBD TBD TBD
¹Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the installation instructions for information about set length and additional
refrigerant charge required.
²HACR type circuit breaker of fuse.
³Refer to National Electrical Code manual to determine wire, fuse and disconnect size requirements.
Air
Physical Data/Electrical Data
RP14 Series
8