Specification Sheet

Air
Airflow Performance Data
RH1P- Series
9
External Static Pressure—Inches W.C. [kPa]
PSC CFM [L/s] Air Delivery/RPM/Watts—115/208/480V Volts
RPM 822
Blower Size/
Motor
HP [W]
# of Speed
6024ST
with 30 kW
Heater
858
Motor
Speed
from
Factory
885
Manufacturer
Recommended
Air-Flow Range
(Min/Max) CFM
Motor
Speed
931 958
Watts 540 519 506 484 459
10x10
1/2 HP [373]
2 Speed
High
CFM 1514 [714] 1411 [666] 1315 [621]
RPM
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
1061 1069
RPM 883 922 959 1001 1015
1078
Model
No.
RH1P
4221ST
No Heater
4221ST
with 20 kW
Heater
4821ST/
4824ST
No Heater
3617ST/
3621ST
with 18 kW
Heater
Watts 442 407 386 376 365
10x8
1/3 HP [249]
2 Speed
4821ST/
4824ST
with 25 kW
Heater
RPM
High
1241/1537 CFM
[580/725 L/s]
High
CFM 1094 [516] 1034 [488] 978 [462]
Low
CFM 1493 [705] 1449 [684] 1363 [643] 1287 [607]
RPM 1049 1067 1085
1211 [571]
Watts 710 702 677
RPM 870 882
6024ST
No Heater
925 957 992
828
860 878 890
Watts 514 508 490 461 431
10x10
1/2 HP [373]
2 Speed
High
CFM
1001
1414 [667] 1311 [619] 1215 [573]
RPM 1067 1080 1094
Watts 735 718 705 695 678
High
1225/1500 CFM
[538/667 L/s]
Low
CFM 1423 [672] 1379 [651] 1293 [610] 1217 [574] 1141 [538]
Watts 700 678 665
RPM 812 861 912 943 973
Watts 554 545 526 508 491
10x10
3/4 HP [559]
2 Speed
High
CFM 1824 [861] 1767 [834] 1653 [780]
RPM 1102 1112 1121
11x11
3/4 HP [559]
2 Speed
High
CFM
High
1395/1824 CFM
[658/861 L/s]
Low
CFM 1488 [702] 1419 [670] 1466 [692] 1430 [675] 1395 [658]
Watts
871 830 770
RPM 862 899 935 965 995
Watts 534 525 506 488 471
10x10
3/4 HP [559]
2 Speed
High
CFM 1724 [814] 1667 [787] 1553 [733]
RPM
High
1116
1054/1148 CFM
[497/542 L/s]
Low
CFM 1151 [543] 1120 [529] 1091 [515] 1054 [497] 1012 [478]
1119 1130
1867 [881] 1816 [857] 1763 [832]
Watts 445 424 387
RPM
High
1225/1500 CFM
[695/796 L/s]
Low
CFM 1418 [669] 1349 [637] 1396 [659] 1360 [642] 1325 [625]
Watts
810 780 730
RPM 764 803 824 856 886
Watts 778 756 733 715 701
11x11
3/4 HP [559]
2 Speed
High
CFM 1967 [928] 1916 [904] 1863 [879]
RPM 948 959 991
989 1005 1020
High
1225/1500 CFM
[695/796 L/s]
High
1766/1965 CFM
[833/927 L/s]
Low
CFM 1866 [881] 1833 [865] 1806 [852] 1772 [836] 1710 [807]
Watts
850 827 816
Low
CFM 1796 [848] 1763 [832] 1736 [819] 1702 [803] 1640 [774]
Watts 818 795 780
115V/208V/480V Airflow Performance Data—RH1P- (PSC Motor)
Notes: • All 208/240V PSC motors have voltage taps for 208 and 240 volts.
All 208/240V PSC motors are shipped on high speed and 240 volts.
All 115V PSC motors are shipped on high speed.
If the application external static is less than 0.5" WC, adjust the motor speed to
the low static speed as described below:
• Unplug the black motor wire off the relay on the control board and
plug in the red motor wire.
• Replace the cap on the black motor wire.
Voltage change (208/240V motors):
• Move the orange lead to transformer 208V tap from 240V tap.
Replace the wire cap on 240V tap.
• Unplug the purple motor wire off the transformer and plug in the
yellow motor wire.
• Replace the cap on the purple motor wire.
All 480V PSC motors are shipped on high speed.
• If the application external static is less than 0.5" WC, adjust the motor speed to
the low static speed as described below for 3-ton through 4-ton air handlers.
• Unplug the black motor wire off the relay and remove the cap from
the red motor wire.
• Plug the red motor wire to the relay and connect the black motor
wire with the yellow motor wire.
• For 5-ton air handler, unplug the black motor wire off the relay and plug in the red
motor wire, then cap the black motor wire. There is no yellow motor wire on 5-ton
air handler.
WARNING: Do not connect red motor wire with yellow motor wire in any circumstance on
480V PSC motors. Connecting red motor wire with yellow motor wire will result in
permanent motor damage.
The above airflow table lists the airflow information for air handlers without heater and air
handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kW)
than the maximum heater kit is installed. Approximate Airflow = Airflow without heater -
(Airflow without heater - Airflow with maximum heater) x (N kW/maximum heater kW)
[ ] Designates Metric Conversions