User Manual
5
Physical Data and Specifications
R962V
MODEL NUMBERS
R962V0403
A17M4CAP
R962V0603
A17M4SCAP
R962V0703
A17M4SCAP
R962V0705
A21M4SCAP
R962V0855
A21M4SCAP
R962V1005
A21M4SCAP
R962V1155A
24M4SCAP
HIGH FIRE INPUT BTU/HR [kW] ➀
42,000 [12.31] 56,000 [16.41] 70,000 [20.50] 70,000 [20.50] 84,000 [24.61] 98,000 [28.72] 112,000 [32.82]
LOW FIRE INPUT 29,400 [8.61] 39,200 [11.49] 49,000 [14.36] 49,000 [14.36] 58,800 [17.23] 68,600 [20.11] 78,400 [23.00]
HEATING CAPACITY BTU/HR [kW] 41,000 [12.02] 55,000 [16.12] 68,000 [19.93] 68,000 [19.93] 82,000 [24.03] 95,000 [27.84] 109,000 [31.94]
HIGH ALTITUDE OUTPUT
10% DERATE [kW] ➁
36,288 [10.64] 48,384 [14.18] 60,480 [17.72] 60,480 [17.72] 72,756 [21.27] 84,672 [24.81] 96,768 [28.36]
BLOWER (D x W) [mm]
11 x 7
[279 x 178]
11 x 8
[279 x 203]
11 x 8
[279 x 203]
11 x 10
[279 x 254]
11 x 10
[279 x 254]
11 x 10
[279 x 254]
11 x 11
[279 x 279]
MOTOR H.P. [W]–TYPE
1/2 [373]
VS-CT(ECM)
1/2 [373]
VS-CT(ECM)
1/2 [373]
VS-CT(ECM)
1 [746]
VS-CT(ECM)
1 [746]
VS-CT(ECM)
1 [746]
VS-CT(ECM)
1 [746]
VS-CT(ECM)
MIN. CIRCUIT AMPACITY 8 8 8 12 12 12 12
MIN. OVERLOAD PROTECTION
DEVICE
15 15 15 20 20 15 15
MAX. OVERLOAD PROTECTION
DEVICE
15 15 15 20 20 15 15
MINIMUM EXT. STATIC
PRESSURE (IN. W.C.) [kPa]
.18 [.045] .20 [.050] .23 [.057] .23 [.057] .28 [.070] .28 [.070] .28 [.070]
MAXIMUM EXT. STATIC
PRESSURE (IN. W.C.) [kPa]
0.9 [0.22] 0.9 [0.22] 0.9 [0.22] 0.9 [0.22] 0.9 [0.22] 0.9 [0.22] 0.9 [0.22]
HEATING HI CFM [L/s] 1150 [543] 1250 [590] 1000 [472] 1332 [629l] 1850 [873] 1965 [927] 1700 [802]
HEATING LO CFM [L/s] 870 [411] 1025 [484] 875 [413] 1121 [529] 1470 [694] 1710 [807] 1450 [684l]
COOLING HI CFM [L/s] 1125 [531] 1125 [531] 1125 [531] 1800 [850] 1800 [850] 1800 [850] 1800 [850]
COOLING LOCFM [L/s] 731 [345] 731 [345] 731 [345] 1170 [552] 1170 [552] 1170 [552] 1170 [552]
TEMPERATURE RISE-HIGH FIRE
RANGE IN DEGREES °F [°C]
20 - 50
[11 - 28]
30 - 60
[17 - 33]
40 - 70
[22 - 39]
30 - 60
[17 - 33]
30 - 60
[17 - 33]
40 - 70
[22 - 39]
45 - 75
[25 - 42]
TEMPERATURE RISE-LOW FIRE
RANGE IN DEGREES °F [°C]
15 - 45
[8 - 25]
20 - 50
[11 - 28]
30 - 60
[17 - 33]
20 - 50
[11 - 28]
20 - 50
[11 - 28]
30 - 60
[17 - 33]
35 - 63
[19 - 36]
APPROX. SHIPPING WEIGHT 128 [58] 128 [58] 132 [60] 139 [63] 147.5 [67] 152 [69] 165 [75]
AFUE ➂
96.00% 96.00% 96.00% 96.00% 96.00% 96.00% 96.00%
NOTES: All models are 115V, 60HZ, 1 phase. Gas connection size for all models is
1
/2" [13 mm] N.P.T.
➀ Installation instructions for high altitude derate.
➁ Canadian installations only.
➂ In accordance with D.O.E. test procedures.
NOTE: Standard model complies with California low NOx requirements up to 40ng/J.
This furnace does not meet air district requirements of 14 ng/J NOx emissions limit, and thus is subject to a mitigation fee of up to $450. This furnace is not eligible for the
Clean Air Furnace Rebate Program: www.CleanAirFurnaceRebate.com.
This furnace is to be installed for propane firing only in air districts requiring 14 ng/J NOx emission limits. Operating in natural gas mode is in violation of these Rules.
[ ] Designates Metric Conversions
Physical Data and Specifications
U.S. and Canadian Models