Specifications

13
1/4 [6.4] 25 [7.6] 40 [12.2] 25 [7.6] 9 [2.7] N/A N/A
1
1
2 Ton 3/8” [9.5] 5/16 [7.9] 25 [7.6] 50 [15.2] 62 [18.9] 58 [17.7] 53 [16.2] 49 [14.9]
3/8* [9.5] 25 [7.6] 50 [15.2] 75 [22.9] 72 [21.9] 70 [21.3] 68 [20.7]
1/4 [6.4] 25 [7.6] N/A N/A N/A N/A N/A
2 Ton 3/8” [9.5] 5/16 [7.9] 25 [7.6] 36 [10.9] 29 [8.8] 23 [7.0] 16 [4.9] 9 [2.7]
3/8* [9.5] 25 [7.6] 50 [15.2] 72 [21.9] 70 [21.3] 68 [20.7] 65 [19.8]
1/4 [6.4] 25 [7.6] N/A N/A N/A N/A N/A
2
1
2 Ton 3/8” [9.5] 5/16 [7.9] 25 [7.6] 49 [14.9] 38 [11.6] 27 [8.3] 17 [5.2] 6 [1.8]
3/8* [9.5] 25 [7.6] 50 [15.2] 68 [20.7] 65 [19.8] 62 [18.9] 58 [17.7]
5/16 [7.9] 25 [7.6] 50 [15.2] 37 [11.3] 22 [6.7] 7 [2.1] N/A
3 Ton 3/8” [9.5]
3/8* [9.5] 25 [7.6] 50 [15.2] 68 [20.7] 63 [19.2] 58 [17.7] 53 [16.2]
5/16 [7.9] 25 [7.6] 23 [7.0] 4 [1.2] N/A N/A N/A
3
1
2 Ton 3/8” [9.5]
3/8* [9.5] 25 [7.6] 50 [15.2] 43 [13.1] 36 [10.9] 30 [9.1] 24 [7.3]
5/16 [7.9] 25 [7.6] 46 [14.0] 38 [11.6] 30 [9.1] 22 [6.7] 15 [4.5]
4 Ton 3/8” [9.5]
3/8* [9.5] 25 [7.6] 50 [15.2] 56 [17.1] 55 [16.8] 53 [16.2] 52 [15.8]
5/16 [7.9] 25 [7.6] 50 [15.2] 56 [17.1] 44 [13.4] 32 [9.8] 20 [6.1]
5 Ton 3/8” [9.5]
3/8* [9.5] 25 [7.6] 50 [15.2] 75 [22.9] 81 [24.7] 79 [24.1] 76 [23.2]
1/4 [6.4] 00008 [2.4] 24 [7.3]
1
1
2 Ton 3/8” [9.5] 5/16 [7.9] 0 00000
3/8* [9.5] 0 00000
1/4 [6.4] 0 3 [0.9] 29 [8.8] 55 [16.8] 81 [24.7] 108 [32.9]
2 Ton 3/8” [9.5] 5/16 [7.9] 0 00000
3/8* [9.5] 0 00000
1/4 [6.4] 0 14 [4.3] 56 [17.1] 98 [29.9] N/A N/A
2
1
2 Ton 3/8” [9.5] 5/16 [7.9] 0 00000
3/8* [9.5] 0 00000
5/16 [7.9] 0 00009
3 Ton 3/8” [9.5]
3/8* [9.5] 0 00000
5/16 [7.9] 00016 [4.9] 35 [10.7] 54 [16.5]
3
1
2 Ton 3/8” [9.5]
3/8* [9.5] 0 00000
5/16 [7.9] 0 00000
4 Ton 3/8” [9.5]
3/8* [9.5] 0 00000
5/16 [7.9] 0 00000
5 Ton 3/8” [9.5]
3/8* [9.5] 0 00000
TABLE 3
LIQUID LINE SIZE OUTDOOR UNIT ABOVE INDOOR COIL
Liquid Line Size
Outdoor Unit Above Indoor Coil
(Cooling Only - Does not apply to Heat Pumps)
System
Capacity
Line Size
Connection Size
(Inch I.D.) [mm]
Line Size
(Inch O.D.)
[mm]
Total Equivalent Length - Feet [m]
Minimum Vertical Separation - Feet [m]
25 [7.8] 50 [15.2] 75 [22.9] 100 [30.5] 125 [38.1] 150 [45.7]
TABLE 4
LIQUID LINE SIZE OUTDOOR UNIT BELOW INDOOR COIL
NOTES: [ ] Designates metric
*Standard
N/A = Application not recommended.
Liquid Line Size
Outdoor Unit Below Indoor Coil
System
Capacity
Line Size
Connection Size
(Inch I.D.) [mm]
Line Size
(Inch I.D.)
[mm]
Total Line Length - Feet [m]
Maximum Vertical Separation - Feet [m]
25 [7.6] 50 [15.2] 75 [22.9] 100 [30.5] 125 [38.1] 150 [45.7]
NOTES:
*Standard Line Size
N/A - Application not recommended.