Specification Sheet
Air
Gross Systems Performance Data
RSNM Series
15
GROSS SYSTEMS PERFORMANCE DATA—RSNM-A036
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
➀
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 1440 [680] 1200 [566] 960 [453] 1440 [680] 1200 [566] 960 [453] 1440 [680] 1200 [566] 960 [453]
DR ➀
.14 .10 .06 .14 .10 .06 .14 .10 .06
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
45.6 [13.36]
28.7 [8.41]
2.4
44.0 [12.90]
26.2 [7.68]
2.3
42.4 [12.43]
23.8 [6.98]
2.3
42.9 [12.57]
33.8 [9.91]
2.3
41.4 [12.13]
30.9 [9.06]
2.3
39.9 [11.69]
28.1 [8.24]
2.2
40.2 [11.78]
38.5 [11.28]
2.3
38.8 [11.37]
35.3 [10.35]
2.3
37.4 [10.96]
32.0 [9.38]
2.3
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
44.8 [13.13]
28.0 [8.21]
2.5
43.2 [12.66]
25.6 [7.50]
2.5
41.6 [12.19]
23.2 [6.80]
2.4
42.1 [12.34]
33.2 [9.73]
2.4
40.6 [11.90]
30.4 [8.91]
2.4
39.2 [11.49]
27.5 [8.06]
2.4
39.4 [11.55]
38.1 [11.17]
2.5
38.0 [11.14]
34.7 [10.17]
2.4
36.6 [10.73]
31.5 [9.23]
2.4
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
43.7 [12.81]
27.4 [8.03]
2.6
42.2 [12.37]
25.0 [7.33]
2.6
40.6 [11.90]
22.7 [6.65]
2.5
41.1 [12.05]
32.6 [9.55]
2.6
39.6 [11.61]
29.8 [8.73]
2.5
38.2 [11.20]
27.0 [7.91]
2.5
38.3 [11.22]
37.5 [10.99]
2.6
37.0 [10.84]
34.1 [9.99]
2.5
35.6 [10.43]
30.9 [9.06]
2.5
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
42.5 [12.46]
26.8 [7.85]
2.7
41.0 [12.02]
24.5 [7.18]
2.7
39.5 [11.58]
22.2 [6.51]
2.7
39.8 [11.66]
31.9 [9.35]
2.7
38.4 [11.25]
29.2 [8.56]
2.6
37.0 [10.84]
26.5 [7.77]
2.6
37.1 [10.87]
36.6 [10.73]
2.7
35.8 [10.49]
33.5 [9.82]
2.7
34.5 [10.11]
30.4 [8.91]
2.6
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
41.2 [12.07]
26.2 [7.68]
2.9
39.7 [11.63]
23.9 [7.00]
2.8
38.3 [11.22]
21.7 [6.36]
2.8
38.5 [11.28]
31.3 [9.17]
2.8
37.2 [10.90]
28.7 [8.41]
2.8
35.8 [10.49]
26.0 [7.62]
2.7
35.8 [10.49]
35.8 [10.49]
2.8
34.5 [10.11]
33.1 [9.70]
2.8
33.3 [9.76]
29.9 [8.76]
2.7
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
39.8 [11.66]
25.6 [7.50]
3.0
38.4 [11.25]
23.4 [6.86]
2.9
37.0 [10.84]
21.2 [6.21]
2.9
37.1 [10.87]
30.8 [9.03]
2.9
35.8 [10.49]
28.1 [8.24]
2.9
34.5 [10.11]
25.5 [7.47]
2.8
34.4 [10.08]
34.4 [10.08]
3.0
33.2 [9.73]
32.5 [9.52]
2.9
32.0 [9.38]
29.5 [8.65]
2.9
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
38.4 [11.25]
25.0 [7.33]
3.1
37.1 [10.87]
22.9 [6.71]
3.1
35.7 [10.46]
20.8 [6.10]
3.0
35.8 [10.49]
30.2 [8.85]
3.1
34.5 [10.11]
27.6 [8.09]
3.0
33.3 [9.76]
25.0 [7.33]
3.0
33.0 [9.67]
33.0 [9.67]
3.1
31.9 [9.35]
31.9 [9.35]
3.0
30.7 [9.00]
29.0 [8.50]
3.0
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
37.1 [10.87]
24.5 [7.18]
3.2
35.8 [10.49]
22.4 [6.56]
3.2
34.5 [10.11]
20.3 [5.95]
3.1
34.5 [10.11]
29.7 [8.70]
3.2
33.3 [9.76]
27.1 [7.94]
3.1
32.1 [9.41]
24.6 [7.21]
3.1
31.7 [9.29]
31.7 [9.29]
3.2
30.6 [8.97]
30.6 [8.97]
3.1
29.5 [8.65]
28.5 [8.35]
3.1
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
36.0 [10.55]
24.0 [7.03]
3.4
34.7 [10.17]
21.9 [6.42]
3.3
33.5 [9.82]
19.9 [5.83]
3.2
33.3 [9.76]
29.1 [8.53]
3.3
32.2 [9.44]
26.7 [7.83]
3.2
31.0 [9.09]
24.2 [7.09]
3.2
30.6 [8.97]
30.6 [8.97]
3.3
29.5 [8.65]
29.5 [8.65]
3.3
28.4 [8.32]
28.1 [8.24]
3.2
GROSS SYSTEMS PERFORMANCE DATA—RSNM-A042
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
➀
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 1680 [793] 1400 [661] 1120 [529] 1680 [793] 1400 [661] 1120 [529] 1680 [793] 1400 [661] 1120 [529]
DR ➀
.15 .11 .07 .15 .11 .07 .15 .11 .07
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
52.7 [15.44]
32.8 [9.61]
2.7
50.9 [14.92]
30.0 [8.79]
2.7
49.0 [14.36]
27.2 [7.97]
2.6
50.0 [14.65]
39.1 [11.46]
2.7
48.2 [14.13]
35.7 [10.46]
2.6
46.5 [13.63]
32.4 [9.50]
2.6
46.4 [13.60]
44.0 [12.90]
2.7
44.8 [13.13]
40.4 [11.84]
2.6
43.2 [12.66]
36.6 [10.73]
2.6
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
51.8 [15.18]
32.0 [9.38]
2.9
50.0 [14.65]
29.3 [8.59]
2.8
48.2 [14.13]
26.5 [7.77]
2.8
49.0 [14.36]
38.3 [11.22]
2.8
47.3 [13.86]
35.0 [10.26]
2.8
45.6 [13.36]
31.7 [9.29]
2.7
45.5 [13.33]
43.6 [12.78]
2.9
43.9 [12.87]
39.7 [11.63]
2.8
42.3 [12.40]
36.0 [10.55]
2.8
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
50.5 [14.80]
31.3 [9.17]
3.0
48.8 [14.30]
28.6 [8.38]
3.0
47.0 [13.77]
25.9 [7.59]
2.9
47.8 [14.01]
37.6 [11.02]
3.0
46.1 [13.51]
34.4 [10.08]
2.9
44.4 [13.01]
31.1 [9.11]
2.9
44.2 [12.95]
42.9 [12.57]
3.0
42.7 [12.51]
39.0 [11.43]
3.0
41.1 [12.05]
35.4 [10.37]
2.9
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
49.1 [14.39]
30.6 [8.97]
3.2
47.3 [13.86]
28.0 [8.21]
3.2
45.6 [13.36]
25.4 [7.44]
3.1
46.3 [13.57]
36.9 [10.81]
3.2
44.7 [13.10]
33.7 [9.88]
3.1
43.0 [12.60]
30.6 [8.97]
3.0
42.8 [12.54]
41.9 [12.28]
3.2
41.3 [12.10]
38.4 [11.25]
3.1
39.8 [11.66]
34.8 [10.20]
3.1
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
47.5 [13.92]
30.0 [8.79]
3.4
45.8 [13.42]
27.4 [8.03]
3.3
44.1 [12.92]
24.8 [7.27]
3.3
44.7 [13.10]
36.2 [10.61]
3.3
43.1 [12.63]
33.1 [9.70]
3.3
41.6 [12.19]
30.0 [8.79]
3.2
41.2 [12.07]
41.2 [12.07]
3.3
39.7 [11.63]
37.8 [11.08]
3.3
38.3 [11.22]
34.3 [10.05]
3.2
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
45.9 [13.45]
29.3 [8.59]
3.5
44.3 [12.98]
26.8 [7.85]
3.5
42.7 [12.51]
24.3 [7.12]
3.4
43.1 [12.63]
35.6 [10.43]
3.5
41.6 [12.19]
32.6 [9.55]
3.4
40.1 [11.75]
29.5 [8.65]
3.4
39.6 [11.61]
39.6 [11.61]
3.5
38.2 [11.20]
37.2 [10.90]
3.4
36.8 [10.79]
33.8 [9.91]
3.4
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
44.4 [13.01]
28.7 [8.41]
3.7
42.9 [12.57]
26.3 [7.71]
3.6
41.3 [12.10]
23.8 [6.98]
3.6
41.7 [12.22]
35.0 [10.26]
3.6
40.2 [11.78]
32.0 [9.38]
3.6
38.8 [11.37]
29.0 [8.50]
3.5
38.2 [11.20]
38.2 [11.20]
3.7
36.8 [10.79]
36.7 [10.76]
3.6
35.5 [10.40]
33.3 [9.76]
3.5
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
43.3 [12.69]
28.1 [8.24]
3.9
41.7 [12.22]
25.7 [7.53]
3.8
40.2 [11.78]
23.3 [6.83]
3.7
40.5 [11.87]
34.4 [10.08]
3.8
39.1 [11.46]
31.5 [9.23]
3.7
37.7 [11.05]
28.5 [8.35]
3.7
37.0 [10.84]
37.0 [10.84]
3.8
35.7 [10.46]
35.7 [10.46]
3.8
34.4 [10.08]
32.8 [9.61]
3.7
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
42.4 [12.43]
27.5 [8.06]
4.0
40.9 [11.99]
25.2 [7.39]
3.9
39.4 [11.55]
22.8 [6.68]
3.9
39.7 [11.63]
33.8 [9.91]
4.0
38.3 [11.22]
30.9 [9.06]
3.9
36.9 [10.81]
28.0 [8.21]
3.8
36.1 [10.58]
36.1 [10.58]
4.0
34.9 [10.23]
34.9 [10.23]
3.9
33.6 [9.85]
32.3 [9.47]
3.9
DR —Depression ratio
dbE —Entering air dry bulb
wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input
NOTES: ➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].