Specification Sheet

GROSS SYSTEMS PERFORMANCE DATA—RSNM-A048
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 1860 [878] 1550 [732] 1240 [585] 1860 [878] 1550 [732] 1240 [585] 1860 [878] 1550 [732] 1240 [585]
DR
.12 .08 .03 .12 .08 .03 .12 .08 .03
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
60.4 [17.70]
36.5 [10.70]
2.9
58.3 [17.09]
33.4 [9.79]
2.9
56.2 [16.47]
30.3 [8.88]
2.8
56.4 [16.53]
44.0 [12.90]
2.9
54.4 [15.94]
40.2 [11.78]
2.9
52.4 [15.36]
36.5 [10.70]
2.8
53.2 [15.59]
50.0 [14.65]
2.9
51.3 [15.03]
45.8 [13.42]
2.9
49.5 [14.51]
41.6 [12.19]
2.8
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
58.5 [17.14]
35.6 [10.43]
3.1
56.4 [16.53]
32.6 [9.55]
3.0
54.4 [15.94]
29.5 [8.65]
3.0
54.4 [15.94]
43.0 [12.60]
3.1
52.5 [15.39]
39.4 [11.55]
3.0
50.6 [14.83]
35.7 [10.46]
3.0
51.2 [15.01]
49.3 [14.45]
3.1
49.4 [14.48]
45.0 [13.19]
3.0
47.6 [13.95]
40.8 [11.96]
3.0
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
56.8 [16.65]
34.8 [10.20]
3.2
54.8 [16.06]
31.9 [9.35]
3.2
52.8 [15.47]
28.9 [8.47]
3.1
52.7 [15.44]
42.2 [12.37]
3.2
50.9 [14.92]
38.6 [11.31]
3.2
49.0 [14.36]
35.0 [10.26]
3.1
49.5 [14.51]
48.5 [14.21]
3.2
47.8 [14.01]
44.3 [12.98]
3.2
46.0 [13.48]
40.1 [11.75]
3.1
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
55.2 [16.18]
34.1 [9.99]
3.4
53.3 [15.62]
31.2 [9.14]
3.3
51.3 [15.03]
28.3 [8.29]
3.3
51.2 [15.01]
41.6 [12.19]
3.4
49.4 [14.48]
38.0 [11.14]
3.3
47.6 [13.95]
34.5 [10.11]
3.3
48.0 [14.07]
47.5 [13.92]
3.4
46.3 [13.57]
43.6 [12.78]
3.3
44.6 [13.07]
39.6 [11.61]
3.3
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
53.7 [15.74]
33.5 [9.82]
3.6
51.8 [15.18]
30.7 [9.00]
3.5
50.0 [14.65]
27.8 [8.15]
3.4
49.7 [14.57]
40.9 [11.99]
3.6
47.9 [14.04]
37.4 [10.96]
3.5
46.2 [13.54]
34.0 [9.96]
3.4
46.5 [13.63]
46.5 [13.63]
3.6
44.9 [13.16]
43.1 [12.63]
3.5
43.2 [12.66]
39.0 [11.43]
3.4
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
52.3 [15.33]
32.9 [9.64]
3.7
50.4 [14.77]
30.1 [8.82]
3.7
48.6 [14.24]
27.3 [8.00]
3.6
48.2 [14.13]
40.3 [11.81]
3.7
46.6 [13.66]
36.9 [10.81]
3.7
44.9 [13.16]
33.4 [9.79]
3.6
45.0 [13.19]
45.0 [13.19]
3.7
43.5 [12.75]
42.5 [12.46]
3.7
41.9 [12.28]
38.5 [11.28]
3.6
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
50.8 [14.89]
32.2 [9.44]
3.9
49.0 [14.36]
29.5 [8.65]
3.8
47.2 [13.83]
26.7 [7.83]
3.8
46.8 [13.72]
39.6 [11.61]
3.9
45.1 [13.22]
36.2 [10.61]
3.8
43.5 [12.75]
32.9 [9.64]
3.7
43.6 [12.78]
43.6 [12.78]
3.9
42.0 [12.31]
41.9 [12.28]
3.8
40.5 [11.87]
38.0 [11.14]
3.7
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
49.2 [14.42]
31.4 [9.20]
4.0
47.5 [13.92]
28.7 [8.41]
4.0
45.8 [13.42]
26.1 [7.65]
3.9
45.2 [13.25]
38.8 [11.37]
4.0
43.6 [12.78]
35.5 [10.40]
4.0
42.0 [12.31]
32.2 [9.44]
3.9
42.0 [12.31]
42.0 [12.31]
4.0
40.5 [11.87]
40.5 [11.87]
4.0
39.1 [11.46]
37.3 [10.93]
3.9
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
47.5 [13.92]
30.5 [8.94]
4.2
45.8 [13.42]
27.9 [8.18]
4.1
44.2 [12.95]
25.3 [7.41]
4.1
43.5 [12.75]
37.9 [11.11]
4.2
41.9 [12.28]
34.7 [10.17]
4.1
40.4 [11.84]
31.4 [9.20]
4.1
40.3 [11.81]
40.3 [11.81]
4.2
38.9 [11.40]
38.9 [11.40]
4.1
37.4 [10.96]
36.5 [10.70]
4.1
GROSS SYSTEMS PERFORMANCE DATA—RSNM-A060
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 2280 [1076] 1900 [897] 1520 [717] 2280 [1076] 1900 [897] 1520 [717] 2280 [1076] 1900 [897] 1520 [717]
DR
.10 .07 .03 .10 .07 .03 .10 .07 .03
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
77.1 [22.60]
48.5 [14.21]
3.7
74.4 [21.80]
44.4 [13.01]
3.7
71.7 [21.01]
40.2 [11.78]
3.6
73.9 [21.66]
57.1 [16.73]
3.7
71.3 [20.90]
52.2 [15.30]
3.6
68.7 [20.13]
47.4 [13.89]
3.5
71.2 [20.87]
64.9 [19.02]
3.7
68.7 [20.13]
59.4 [17.41]
3.6
66.2 [19.40]
53.8 [15.77]
3.5
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
74.6 [21.86]
46.7 [13.69]
3.9
72.0 [21.10]
42.7 [12.51]
3.9
69.4 [20.34]
38.7 [11.34]
3.8
71.4 [20.93]
55.2 [16.18]
3.9
68.9 [20.19]
50.5 [14.80]
3.8
66.4 [19.46]
45.8 [13.42]
3.7
68.7 [20.13]
63.0 [18.46]
3.9
66.3 [19.43]
57.6 [16.88]
3.8
63.9 [18.73]
52.3 [15.33]
3.7
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
72.4 [21.22]
45.4 [13.31]
4.2
69.8 [20.46]
41.5 [12.16]
4.1
67.3 [19.72]
37.6 [11.02]
4.0
69.2 [20.28]
54.0 [15.83]
4.1
66.7 [19.55]
49.3 [14.45]
4.0
64.3 [18.84]
44.7 [13.10]
4.0
66.5 [19.49]
61.7 [18.08]
4.1
64.2 [18.82]
56.5 [16.56]
4.0
61.8 [18.11]
51.2 [15.01]
4.0
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
70.3 [20.60]
44.5 [13.04]
4.4
67.9 [19.90]
40.7 [11.93]
4.3
65.4 [19.17]
36.9 [10.81]
4.2
67.1 [19.67]
53.1 [15.56]
4.3
64.8 [18.99]
48.5 [14.21]
4.2
62.4 [18.29]
44.0 [12.90]
4.2
64.5 [18.90]
60.8 [17.82]
4.3
62.2 [18.23]
55.6 [16.29]
4.2
59.9 [17.55]
50.5 [14.80]
4.2
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
68.4 [20.05]
43.8 [12.84]
4.6
66.0 [19.34]
40.1 [11.75]
4.5
63.6 [18.64]
36.3 [10.64]
4.4
65.2 [19.11]
52.4 [15.36]
4.5
62.9 [18.43]
47.9 [14.04]
4.5
60.6 [17.76]
43.4 [12.72]
4.4
62.5 [18.32]
60.2 [17.64]
4.5
60.3 [17.67]
55.0 [16.12]
4.5
58.1 [17.03]
49.9 [14.62]
4.4
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
66.5 [19.49]
43.1 [12.63]
4.8
64.2 [18.82]
39.4 [11.55]
4.7
61.8 [18.11]
35.8 [10.49]
4.7
63.3 [18.55]
51.7 [15.15]
4.8
61.1 [17.91]
47.3 [13.86]
4.7
58.8 [17.23]
42.9 [12.57]
4.6
60.6 [17.76]
59.5 [17.44]
4.7
58.5 [17.14]
54.4 [15.94]
4.7
56.4 [16.53]
49.3 [14.45]
4.6
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
64.5 [18.90]
42.3 [12.40]
5.0
62.3 [18.26]
38.7 [11.34]
5.0
60.0 [17.58]
35.1 [10.29]
4.9
61.3 [17.97]
50.9 [14.92]
5.0
59.2 [17.35]
46.6 [13.66]
4.9
57.0 [16.71]
42.2 [12.37]
4.8
58.6 [17.17]
58.6 [17.17]
5.0
56.6 [16.59]
53.7 [15.74]
4.9
54.5 [15.97]
48.7 [14.27]
4.8
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
62.4 [18.29]
41.2 [12.07]
5.3
60.2 [17.64]
37.7 [11.05]
5.2
58.0 [17.00]
34.1 [9.99]
5.1
59.2 [17.35]
49.8 [14.59]
5.2
57.1 [16.73]
45.5 [13.33]
5.1
55.1 [16.15]
41.3 [12.10]
5.0
56.5 [16.56]
56.5 [16.56]
5.2
54.6 [16.00]
52.6 [15.42]
5.1
52.6 [15.42]
47.7 [13.98]
5.0
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
60.1 [17.61]
39.5 [11.58]
5.5
58.0 [17.00]
36.1 [10.58]
5.4
55.9 [16.38]
32.8 [9.61]
5.3
56.9 [16.68]
48.1 [14.10]
5.4
54.9 [16.09]
44.0 [12.90]
5.3
52.9 [15.50]
39.9 [11.69]
5.2
54.2 [15.88]
54.2 [15.88]
5.4
52.3 [15.33]
51.1 [14.98]
5.3
50.4 [14.77]
46.3 [13.57]
5.2
DR —Depression ratio
dbE —Entering air dry bulb
wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power—KW input
NOTES: When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
[ ] Designates Metric Conversions
16
SYSTEMS PERFORMANCE—RSNM- SERIES