PACKAGE AIR CONDITIONERS FORM NO. A11-186 REV. 5 Supersedes Form No. A11-186 Rev. 4 Featuring Industry Standard R-410A Refrigerant RSNM- HIGH EFFICIENCY 13-SEER SERIES NOMINAL SIZES 2-5 TONS [7-17.6 kW] RSPM- SUPER HIGH EFFICIENCY 14-SEER SERIES NOMINAL SIZES 2-5 TON [7-17.6 kW] (14 SEER ONLY) “Proper sizing and installation of equipment is critical to achieve optimal performance. Split system air conditioners and heat pumps must be matched with appropriate coil components to meet ENERGY STAR criteria.
TABLE OF CONTENTS Unit Features & Benefits ..............................................................................3-6 Model Identification Options ............................................................................7 General Data RSNM- Series ........................................................................................8-10 RSPM- Series ......................................................................................11-13 Performance Data RSNM- Cooling Series .................
UNIT FEATURES & BENEFITS—RSNM/RSPM- SERIES 2 1 The RSNM/RSPM series of Package Air Conditioners are designed to be the most efficient, quickest to install, easiest to service, and most reliable units in the industry - while still maintaining an affordable price. This platform provides you with a full line of nominal capacities from 2 through 5 tons utilizing earth-friendly R-410A refrigerant.
UNIT FEATURES & BENEFITS—RSNM/RSPM- SERIES 3 2 While other manufacturers have chosen to use pre-painted steel in their equipment, which exposes raw edges and invites rust and sharp edges, Rheem package equipment uses a powder-coat paint system, rated at 1000 hour salt spray per ASTM B117. The powder-coat process also greatly diminishes and dulls sharp edges, reducing the occurrence of cuts and torn clothes.
UNIT FEATURES & BENEFITS—RSNM/RSPM- SERIES The controls are located in a large, easy-to-access control box ( 11 ), which provides plenty of space in which to troubleshoot. The transformer ( 12 ) is protected by an in-line fuse, which protects the transformer during a low-voltage electrical short. The lowvoltage ( 13 ) and high-voltage ( 14 ) wiring connections are easily accessed and have ample room around which to maneuver.
UNIT FEATURES & BENEFITS—RSNM/RSPM- SERIES Foil-faced insulation is securely glued and captured to the cabinet. On the base of the unit, closed-cell insulation is used to prevent moisture from being absorbed and help reduce mold content to provide better indoor air quality. High and low refrigerant pressure can easily and accurately be measured using the two gauge ports ( 15 ) located inside the control box.
MODEL IDENTIFICATION—RSNM/RSPM- SERIES R S N M — A 036 J K 010 Heating Capacity (Factory Installed) 000 = No Resistance Heat 005 = 05 KW Resistance Heat 007 = 07 KW Resistance Heat 010 = 10 KW Resistance Heat 015 = 15 KW Resistance Heat 020 = 20 KW Resistance Heat * Drive Package K = Direct Drive Electrical Designation J = 208-230V—1PH—60 Hz C = 208-230V—3PH—60 Hz Nominal Cooling Capacity (BTUH) [kW] 024 = 24,000 [7.03] 030 = 30,000 [8.79] 036 = 36,000 [10.55] 042 = 42,000 [12.31] 043 = 42,000 [12.
GENERAL DATA—RSNM- SERIES NOMINAL SIZES 2-5 TONS [7-17.6 kW] Model RSNM- Series A024JK Cooling Performance1 Gross Cooling Capacity Btu [kW] EER/SEER2 A030JK A036CK A036JK 24,800 [7.27] 11.3/13 30,000 [8.79] 11.5/13 37,200 [10.9] 11.3/13 CONTINUED 37,200 [10.9] 11.3/13 800/800 [378/378] 23,800 [6.97] 1000/1000 [472/472] 28,800 [8.44] 1200/1200 [566/566] 35,800 [10.49] 1200/1200 [566/566] 35,800 [10.49] Net Sensible Capacity Btu [kW] 18,400 [5.39] 22,200 [6.
GENERAL DATA—RSNM- SERIES NOMINAL SIZES 2-5 TONS [7-17.6 kW] Model RSNM- Series A042CK Cooling Performance1 Gross Cooling Capacity Btu [kW] EER/SEER2 A042JK A048CK A048JK 43,000 [12.6] 11.1/13 43,000 [12.6] 11.1/13 48,000 [14.06] 11.3/13 CONTINUED 48,000 [14.06] 11.3/13 1400/1400 [661/661] 41,500 [12.16] 1400/1400 [661/661] 41,500 [12.16] 1600/1550 [755/731] 46,000 [13.48] 1600/1550 [755/731] 46,000 [13.48] Net Sensible Capacity Btu [kW] 31,500 [9.23] 31,500 [9.23] 35,500 [10.
GENERAL DATA—RSNM- SERIES NOMINAL SIZES 2-5 TON [7-17.6 kW] Model RSNM- Series Cooling Performance1 Gross Cooling Capacity Btu [kW] EER/SEER2 Nominal CFM/AHRI Rated CFM [L/s] AHRI Net Cooling Capacity Btu [kW] Net Sensible Capacity Btu [kW] Net Latent Capacity Btu [kW] Net System Power kW A060CK A060JK 63,000 [18.46] 11.3/13 63,000 [18.46] 11.3/13 2000/1900 [944/897] 60,000 [17.58] 2000/1900 [944/897] 60,000 [17.58] 45,000 [13.18] 45,000 [13.18] 15,000 [4.4] 15,000 [4.4] 5.31 5.
GENERAL DATA—RSPM- SERIES NOMINAL SIZES 2-5 TON [7-17.6 kW] Model RSPM- Series A024JK Cooling Performance1 Gross Cooling Capacity Btu [kW] EER/SEER2 A030JK A036CK A036JK 25,200 [7.38] 12.4/14 30,400 [8.91] 12.25/14 37,600 [11.02] 12.2/14 CONTINUED 37,600 [11.02] 12.2/14 800/800 [378/378] 24,200 [7.09] 1000/1000 [472/472] 29,200 [8.56] 1200/1200 [566/566] 36,200 [10.61] 1200/1200 [566/566] 36,200 [10.61] Net Sensible Capacity Btu [kW] 18,800 [5.51] 23,000 [6.74] 27,700 [8.12] 27,700 [8.
GENERAL DATA—RSPM- SERIES NOMINAL SIZES 2-5 TONS [7-17.6 kW] Model RSPM- Series A042CK Cooling Performance1 Gross Cooling Capacity Btu [kW] EER/SEER2 A042JK A043CK A043JK 43,500 [12.75] 11.85/14 43,500 [12.75] 11.85/14 43,000 [12.6] 12/14 CONTINUED 43,000 [12.6] 12/14 1400/1400 [661/661] 42,000 [12.31] 1400/1400 [661/661] 42,000 [12.31] 1400/1400 [661/661] 42,000 [12.31] 1400/1400 [661/661] 42,000 [12.31] Net Sensible Capacity Btu [kW] 32,500 [9.52] 32,500 [9.52] 32,000 [9.38] 32,000 [9.
GENERAL DATA—RSPM- SERIES NOMINAL SIZES 2-5 TONS [7-17.6 kW] Model RSPM- Series A048CK A048JK A060CK A060JK 49,000 [14.36] 12.6/14 49,000 [14.36] 12.6/14 64,000 [18.75] 12.35/14 64,000 [18.75] 12.35/14 1600/1600 [755/755] 47,000 [13.77] 1600/1600 [755/755] 47,000 [13.77] 2000/1900 [944/897] 61,000 [17.87] 2000/1900 [944/897] 61,000 [17.87] Net Sensible Capacity Btu [kW] 36,400 [10.67] 36,400 [10.67] 45,500 [13.33] 45,500 [13.33] Net Latent Capacity Btu [kW] 10,600 [3.11] 10,600 [3.
SYSTEMS PERFORMANCE—RSNM- SERIES GROSS SYSTEMS PERFORMANCE DATA—RSNM-A024 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀ 960 [453] .12 71°F [21.7°C] 800 [378] .08 640 [302] .03 960 [453] .12 67°F [19.4°C] 800 [378] .08 640 [302] .03 960 [453] .12 63°F [17.2°C] 800 [378] .08 640 [302] .03 Total BTUH [kW] 75 Sens BTUH [kW] [23.9] Power 30.5 [8.94] 19.0 [5.57] 1.5 29.4 [8.62] 17.4 [5.10] 1.5 28.4 [8.32] 15.8 [4.63] 1.5 28.5 [8.35] 22.4 [6.56] 1.5 27.5 [8.06] 20.5 [6.01] 1.5 26.
SYSTEMS PERFORMANCE—RSNM- SERIES GROSS SYSTEMS PERFORMANCE DATA—RSNM-A036 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀ O U T D O O R D R Y B U L B T E M P E R A T U R E 71°F [21.7°C] 1200 [566] .10 960 [453] .06 1440 [680] .14 67°F [19.4°C] 1200 [566] .10 960 [453] .06 1440 [680] .14 63°F [17.2°C] 1200 [566] .10 960 [453] .06 Total BTUH [kW] 45.6 [13.36] 75 Sens BTUH [kW] 28.7 [8.41] [23.9] 2.4 Power 44.0 [12.90] 26.2 [7.68] 2.3 42.4 [12.43] 23.8 [6.98] 2.3 42.9 [12.57] 33.8 [9.
SYSTEMS PERFORMANCE—RSNM- SERIES GROSS SYSTEMS PERFORMANCE DATA—RSNM-A048 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀ O U T D O O R D R Y B U L B T E M P E R A T U R E 71°F [21.7°C] 1550 [732] .08 1240 [585] .03 1860 [878] .12 67°F [19.4°C] 1550 [732] .08 1240 [585] .03 1860 [878] .12 63°F [17.2°C] 1550 [732] .08 1240 [585] .03 Total BTUH [kW] 60.4 [17.70] 75 Sens BTUH [kW] 36.5 [10.70] [23.9] 2.9 Power 58.3 [17.09] 33.4 [9.79] 2.9 56.2 [16.47] 30.3 [8.88] 2.8 56.4 [16.53] 44.
SYSTEMS PERFORMANCE—RSPM- SERIES GROSS SYSTEMS PERFORMANCE DATA—RSPM-A024 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀ 960 [453] .10 71°F [21.7°C] 800 [378] .06 640 [302] .01 960 [453] .10 67°F [19.4°C] 800 [378] .06 640 [302] .01 960 [453] .10 63°F [17.2°C] 800 [378] .06 640 [302] .01 Total BTUH [kW] 75 Sens BTUH [kW] [23.9] Power 30.9 [9.06] 19.4 [5.69] 1.4 29.8 [8.73] 17.8 [5.22] 1.3 28.7 [8.41] 16.1 [4.72] 1.3 29.0 [8.50] 22.9 [6.71] 1.4 28.0 [8.21] 20.9 [6.13] 1.3 26.
SYSTEMS PERFORMANCE—RSPM- SERIES GROSS SYSTEMS PERFORMANCE DATA—RSPM-A036 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀ O U T D O O R D R Y B U L B T E M P E R A T U R E 71°F [21.7°C] 1200 [566] .09 960 [453] .04 1440 [680] .12 67°F [19.4°C] 1200 [566] .09 960 [453] .04 1440 [680] .12 63°F [17.2°C] 1200 [566] .09 960 [453] .04 Total BTUH [kW] 34.5 [10.11] 75 Sens BTUH [kW] 21.1 [6.18] [23.9] 2.1 Power 33.3 [9.76] 19.3 [5.66] 2.0 32.0 [9.38] 17.5 [5.13] 2.0 31.6 [9.26] 26.6 [7.
SYSTEMS PERFORMANCE—RSPM- SERIES GROSS SYSTEMS PERFORMANCE DATA—RSPM-A043CK ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀ O U T D O O R D R Y B U L B T E M P E R A T U R E 71°F [21.7°C] 1400 [661] .09 1120 [529] .12 1680 [793] .05 67°F [19.4°C] 1400 [661] .09 1120 [529] .12 1680 [793] .05 63°F [17.2°C] 1400 [661] .09 1120 [529] .12 Total BTUH [kW] 51.7 [15.2] 75 Sens BTUH [kW] 31.5 [9.2] [23.9] 2.6 Power 49.9 [14.6] 27.0 [7.9] 2.6 48.1 [14.1] 22.8 [6.7] 2.5 49.5 [14.5] 39.5 [11.
SYSTEMS PERFORMANCE—RSPM- SERIES GROSS SYSTEMS PERFORMANCE DATA—RSPM-A048 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE CFM [L/s] DR ➀ O U T D O O R D R Y B U L B T E M P E R A T U R E 71°F [21.7°C] 1600 [755] .09 1280 [604] .04 1920 [906] .12 67°F [19.4°C] 1600 [755] .09 1280 [604] .04 1920 [906] .12 63°F [17.2°C] 1600 [755] .09 1280 [604] .04 Total BTUH [kW] 61.1 [17.91] 75 Sens BTUH [kW] 37.7 [11.05] [23.9] 2.5 Power 59.0 [17.29] 34.5 [10.11] 2.4 56.8 [16.65] 31.2 [9.14] 2.4 57.3 [16.79] 44.
Low 5.0 [17.6] 1750/2250 1400/1800 1225/1575 1050/1350 875/1125 700/900 Manufacturer Recommended Air-Flow Range (Min/Max) CFM [ ] Designates Metric Conversions Low Low 3.0 [10.55] 4.0 [14.07] Low 2.5 [8.79] Low Low 2.0 [7.03] 3.5 [12.
Low 5.0 [17.6] 1750/2250 1400/1800 1225/1575 1050/1350 875/1125 700/900 Manufacturer Recommended Air-Flow Range (Min/Max) CFM [ ] Designates Metric Conversions Low Low 3.0 [10.55] 4.0 [14.07] Low 2.5 [8.79] Low Low 2.0 [7.03] 3.5 [12.
Low (Tap 2) 5.0 [17.6] 1750/2250 1400/1800 1225/1575 1050/1350 875/1125 700/900 Manufacturer Recommended Air-Flow Range (Min/Max) CFM [ ] Designates Metric Conversions Low (Tap 2) Low (Tap 2) 3.0 [10.55] 4.0 [14.07] Low (Tap 2) 2.5 [8.79] Low (Tap 2) Low (Tap 2) 2.0 [7.03] 3.5 [12.
Low (Tap 2) 5.0 [17.6] 1750/2250 1400/1800 1225/1575 1050/1350 875/1125 700/900 Manufacturer Recommended Air-Flow Range (Min/Max) CFM [ ] Designates Metric Conversions Low (Tap 2) Low (Tap 2) 3.0 [10.55] 4.0 [14.07] Low (Tap 2) 2.5 [8.79] Low (Tap 2) Low (Tap 2) 2.0 [7.03] 3.5 [12.
ELECTRICAL DATA—RSNM- SERIES Evaporator Fan Condenser Motor Compressor Motor Unit Information ELECTRICAL DATA – RSNM SERIES -A024JK -A030JK -A036CK -A036JK -A042CK -A042JK -A048CK -A048JK -A060CK -A060JK Unit Operating Voltage Range 187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253 Minimum Circuit Ampacity 20/20 21/21 20/20 26/26 22/22 27/27 24/24 32/32 28/28 41/41 25/25 25/25 25/25 30/30 25/25 35/35 30/30 40/40 35/35 50/50 30/30
ELECTRICAL DATA—RSPM- SERIES Evaporator Fan Condenser Motor Compressor Motor Unit Information ELECTRICAL DATA – RSPM SERIES Unit Operating Voltage Range Minimum Circuit Ampacity Minimum Overcurrent Protection Device Size Maximum Overcurrent Protection Device Size No. Volts Phase HP RPM Amps (RLA) Amps (LRA) No. Volts Phase HP Amps (FLA) Amps (LRA) No.
A060J A048J A042J A036J A030J A024J Unit Model No. RSNM- No Heat C05J C07J C10J No Heat C05J C07J C10J C15J No Heat C05J C07J C10J C15J No Heat C05J C07J C10J C15J C20J No Heat C05J C07J C10J C15J C20J No Heat C05J C07J C10J C15J C20J — 1 1 2 — 1 1 2 3 — 1 1 2 3 — 1 1 2 3 4 — 1 1 2 3 4 — 1 1 2 3 4 RXQJ-C No. of Heater Kit Elements Nominal kW — 1 1 1 — 1 1 1 2 — 1 1 1 2 — 1 1 1 2 2 — 1 1 1 2 2 — 1 1 1 2 2 No. of Sequence Steps — 3.6/4.8 5.4/7.2 7.2/9.6 — 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4 — 3.
A060C A048C A042C A036C Unit Model No. RSNM- No Heat 10C 15C No Heat 10C 15C 20C No Heat 10C 15C 20C No Heat 10C 15C 20C — 2 3 — 2 3 4 — 2 3 4 — 2 3 4 RXQJ-C No. of Heater Kit Elements Nominal kW — 1 2 — 1 2 2 — 1 2 2 — 1 2 2 No. of Sequence Steps — 7.2/9.6 10.8/14.4 — 7.2/9.6 10.8/14.4 14.4/19.2 — 7.2/9.6 10.8/14.4 14.4/19.2 — 7.2/9.6 10.8/14.4 14.4/19.2 — 24.57/32.76 36.85/49.13 — 24.57/32.76 36.85/49.13 49.12/65.52 — 24.57/32.76 36.85/49.13 49.12/65.52 — 24.57/32.76 36.85/49.13 49.12/65.
A060J A048J A042J A043J A036J A030J A024J Unit Model No. RSPM- No Heat 05J 07J 10J No Heat 05J 07J 10J 15J No Heat 05J 07J 10J 15J No Heat 05J 07J 10J 15J 20J No Heat 05J 07J 10J 15J 20J No Heat 05J 07J 10J 15J 20J — 1 1 2 — 1 1 2 3 — 1 1 2 3 — 1 1 2 3 4 — 1 1 2 3 4 — 1 1 2 3 4 RXQJ-C No. of Heater Kit Elements Nominal kW — 1 1 1 — 1 1 1 2 — 1 1 1 2 — 1 1 1 2 2 — 1 1 1 2 2 — 1 1 1 2 2 No. of Sequence Steps — 3.6/4.8 5.4/7.2 7.2/9.6 — 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4 — 3.6/4.8 5.4/7.2 7.2/9.
A060C A048C A042C A043C A036C Unit Model No. RSPM- No Heat 10C 15C No Heat 10C 15C 20C No Heat 10C 15C 20C No Heat 10C 15C 20C — 2 3 — 2 3 4 — 2 3 4 — 2 3 4 RXQJ-C No. of Heater Kit Elements Nominal kW — 1 2 — 1 2 2 — 1 2 2 — 1 2 2 No. of Sequence Steps — 7.2/9.6 10.8/14.4 — 7.2/9.6 10.8/14.4 14.4/19.2 — 7.2/9.6 10.8/14.4 14.4/19.2 — 7.2/9.6 10.8/14.4 14.4/19.2 — 24.57/32.76 36.85/49.13 — 24.57/32.76 36.85/49.13 49.12/65.52 — 24.57/32.76 36.85/49.13 49.12/65.52 — 24.57/32.76 36.85/49.13 49.12/65.
UNIT DIMENSIONS—RSNM/RSPM- SERIES DIMENSIONS FRONT VIEW Model Height “A” 024, 030, 036, 042, 043 048, 060 29 1/8" 37 1/8" REAR VIEW BOTTOM VIEW ELECTRICAL CONNECTIONS (FRONT) (REAR) [ ] Designates Metric Conversions 31
TYPICAL INSTALLATIONS [ ] Designates Metric Conversions 32
ACCESSORIES ACCESSORY EQUIPMENT Accessory Description Outdoor Thermostat Thermostat Model Application RSNM/RSPM RSNM/RSPM Accessory Model No.
WIRING SCHEMATICS—RSNM- SERIES 34
WIRING SCHEMATICS—RSNM- SERIES 35
WIRING SCHEMATICS—RSNM- SERIES 36
WIRING SCHEMATICS—RSPM- SERIES 37
WIRING SCHEMATICS—RSPM- SERIES 38
WIRING SCHEMATICS—RSPM- SERIES 39
BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLE FROM YOUR RETAILER. GENERAL TERMS OF LIMITED WARRANTY Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable periods stated, in accordance with the terms of the limited warranty. *For Complete Details of the Limited Warranty, Including Applicable Terms and Conditions, See Your Local Installer or Contact the Manufacturer for a Copy.