Technical data
INSTALLATION 
6 
MAINS WATER SUPPLY 
Where the mains water supply pressure exceeds that shown in the table below, 
an  approved  pressure  limiting  valve  is  required. Refer  to the  Owner‟s  Guide 
and Installation  Instructions supplied  with  the  storage  tank for  the  position  of 
the pressure limiting valve. 
Model 
325, 410 
Relief valve setting 
1000 kPa 
Expansion control valve setting * 
850 kPa 
Max. mains supply pressure 
With expansion control valve 
680 kPa 
Without expansion control valve 
800 kPa 
Min. mains supply pressure 
200 kPa 
* Expansion control valve not supplied with the water heater. 
A minimum  water  supply  pressure of 200 kPa is  required  to  enable the  heat 
pump circulator and heat pump system to operate effectively. 
TANK WATER SUPPLY 
If the water heater is supplied with water from a tank supply and a  minimum 
water supply pressure of 200 kPa at the water heater cannot be achieved, then 
a pressure pump system must be installed to allow the heat pump circulator to 
operate and avoid air locks in the circuit. Care must be taken to avoid air locks. 
The cold water line from the supply tank should be adequately sized and fitted 
with a full flow gate valve or ball valve. 
CONDENSATE DRAIN 
A drain  line  should be  fitted to  the  heat  pump  module‟s condensate  drain to 
carry the discharge clear of the water heater. The drain line can be extended 
using  12 mm  rigid  poly  hose or  conduit.  The  pipe work  from the  condensate 
drain should be as short as possible and fall all the way from the water heater 
with no restrictions. It should have no more than three right angle bends in it. 
The outlet of the drain line must be in such a position that flow out of the pipe 
can be easily seen - but arranged so water discharge will not cause damage or 
nuisance. 
The  condensate  drain  line  must not  be  connected to  the  relief valves 
drain lines but may discharge at the same point. 










