Technical data
COMMISSIONING 
29 
Note:  The  heat  pump  may  not  turn  on  after  either  having  just  completed  a 
heating cycle and more hot water is drawn from the water heater or power is 
shut down to the compressor, either during or at the end of a heating cycle. The 
heat pump will wait until the compressor has cooled down and the conditions 
for  start  up  are  favourable  in  order to  protect  the  compressor  from  damage. 
This  will  be  a  minimum  of  forty  five (45)  minutes  and  may  take  up  to 
ninety (90) minutes from the last heating cycle. 
It is important to wait for five (5) minutes after the heat pump has activated to 
ensure it continues to operate and is functioning correctly. 
Explain to the householder or a responsible officer the functions and operation 
of  the  heat  pump  water  heater.  Upon  completion  of  the  installation  and 
commissioning  of  the  water  heating  system,  leave  this  guide  with  the 
householder or a responsible officer. 
TO TURN OFF THE WATER HEATER 
If it is necessary to turn off the water heater on completion of the installation, 
such as on a building site or where the premises are vacant, then: 
  Switch off the electrical supply at the isolating switch to the water heater. 
  Close the cold water isolation valve at the inlet to the water heater. 
DIAGNOSTIC FEATURES OF THE HEAT PUMP CONTROLLER 
An operating mode monitor is located on the front of the heat pump module and 
houses a green and a red LED. 
The  green  LED,  marked  “NORMAL”, 
indicates the current operating mode of the 
heat pump water heater and the red LED, 
marked  “ATTENTION”,  indicates  a  fault 
mode. 
The green LED will emit either a constant glow or a series of flashes, with a 
2 second interval between each series. A series of long green flashes may also 
be emitted. 
The  red  LED  will  emit  a  series  of  flashes,  with  a  2 second  interval  between 
each series, only if there is a particular fault condition with the system. 










