Specification Sheet
Air
Airflow Performance Data
RHML Series
9
Model
No.
RHML
Nominal
Cooling
Capacity
Tons
Motor
Speed
From
Factory
Manufacturer
Recommended
Air-Flow Range
(Min/Max) CFM
Blower Size/
Motor
HP
# of Speeds
Y1, Y2
Speed
Motor
Speed
X-13 Wet Coil No Filter CFM Air Delivery/RPM/Watts-230 Volts
External Static Pressure—Inches W.C. [kPa]
0.1 [.02]
0.2 [.05] 0.3 [.07] 0.4 [.10]
0.5 [.12] 0.6 [.15]
0.7 [.17] 0.8 [.20]
0.9 [.22] 1.0 [.25]
-3621
No Heater
3.0
Y1 Tap 4
Y2 Tap 5
Y1=434/1005 CFM
[204/474] L/s
Y2=703/1328 CFM
[331/626] L/s
10X10
3/4 Hp 5 speed
Y1
Low Static
Tap 2
CFM
919
757 596
434 — —
—
— — —
RPM
567
584 635 691
— —
— — —
—
Watts 83 79 75 71 67
62
58 54 — —
Y2
Low Static
Tap 3
CFM
1128
1067
1007 946 885 824
764
703 — —
RPM 644 691 728
804
884
921
945 986
— —
Watts
131
142 153 164 175
187
— — — —
Y1
High Static
Tap 4
CFM 1005 942 879 816 753 690 — — — —
RPM 597
645 700
790 830 868
— —
— —
Watts 99 108 117 127 136 145 154 164 173 182
Y2
High Static
Tap 5
CFM 1328 1273 1218 1164 1109
1055
1000 945 891 836
RPM
737
773
815 854 907 990
1040
1065 1085 1117
Watts
197
209 221 233
245 257
269 281 293
305
-3621 With
18 kW
Heater
3.0
Y1 Tap 4
Y2 Tap 5
Y1=404/975 CFM
[190/460] L/s
Y2=673/1298 CFM
[317/612] L/s
10X10
3/4 Hp 5 speed
Y1
Low Static
Tap 2
CFM
889
727 566 404
— —
— — —
—
RPM
592
609 660 716 —
—
— — — —
Watts 88 84 80 76 — — — — — —
Y2
Low Static
Tap 3
CFM 1098 1037 977 916 855 794 734 673 — —
RPM
669
716 753 829 909
946
970 1011 — —
Watts 136 147 158 169 180 192 5 5 — —
Y1
High Static
Tap 4
CFM
975
912
849 786 723 660
—
— — —
RPM 622 670 725
815
855 893 — —
—
—
Watts 104 113 122 132 141 150 —
—
— —
Y2
High Static
Tap 5
CFM
1298
1243
1188 1134 1079 1025
970
915 861 806
RPM 762
798
840 879 932 1015
1065
1090 1110 1142
Watts 202
214
226
238 250
262
274
286 298 —
Airflow Performance Data
Notes: • All 208/240V PSC motors have voltage taps for 208 and 240 volts.
• All 208/240V PSC motors are shipped on high speed and 240 volts.
• If the application external static is less than 0.5" WC, adjust the motor speed to the low static speed as described below:
• Unplug the black motor wire off the relay on the control board and plug in the red motor wire.
• Replace the cap on the black motor wire.
• Voltage change (208/240V motors):
• Move the orange lead to transformer 208V tap from 240V tap. Replace the wire cap on 240V tap.
• Unplug the purple motor wire off the transformer and plug in the yellow motor wire.
• Replace the cap on the purple motor wire.
• The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed.
Approximate Airflow = Airflow without heater - (Airflow without heater - Airflow with maximum heater) x (N kW/maximum heater kW)
[ ] Designates Metric Conversions