Specification Sheet

Air
Electrical Data
RHML Series
13
Air Handler
Model
Heater
Model
No.
Heater kW
(208/240V)
(480V)
Ph/Hz
No.
Elements
- kW Per
Type Supply
Circuit
Single Circuit
Multiple Circuit
Circuit
Amps.
Motor
Ampacity
Minimum
Circuit
Ampacity
Maximum
Circuit
Protector
(-)HML
4824
6024
RXBH-1724?07J 5.4/7.2 1/60 2-3.6 SINGLE 26.0/30.0 4.6
39/44 40/45
RXBH-1724?10J 7.2/9.6 1/60 2-4.8 SINGLE 34.6/40.0 4.6
49/56 50/60
RXBH-1724A15J 10.8/14.4 1/60 3-4.8 SINGLE 51.9/60.0 4.6
71/81 80/90
RXBH-1724A15J
3.6/4.8 1/60 1-4.8 MULTIPLE CKT 1 17.3/20.0 4.6
28/31 30/35
7.2/9.6 1/60 2-4.8 MULTIPLE CKT 2 34.6/40.0 0
44/50 45/50
RXBH-1724A18J 12.8/17 1/60 4-4.26 SINGLE 61.8/70.8 4.6
83/95 90/100
RXBH-1724A18J
6.4/8.5 1/60 2-4.26 MULTIPLE CKT 1 30.8/35.4 4.6
45/50 45/50
6.4/8.5 1/60 2-4.6 MULTIPLE CKT 2 30.8/35.4 0
39/45 40/45
RXBH-24A20J 14.4/19.2 1/60 4-4.8 SINGLE 69.2/80 4.6
93/106 100/110
RXBH-24A20J
7.2/9.6 1/60 2-4.8 MULTIPLE CKT 1 34.6/40.0 4.6
49/56 50/60
7.2/9.6 1/60 2-4.8 MULTIPLE CKT 2 34.6/40.0 0
44/50 45/50
RXBH-24A25J 18.0/24.0 1/60 6-4.0 SINGLE 86.4/99.9 4.6
114/131 125/150
RXBH-24A25J
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 1 28.8/33.3 4.6
42/48 45/50
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 2 28.8/33.3 0
36/42 40/45
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 3 28.8/33.3 0
36/42 40/45
RXBH-24A30J
(5-ton only)
21.6/28.8 1/60 6-4.8 SINGLE 103.8/120 4.6
136/156 150/175
RXBH-24A30J
(5-ton only)
7.2/9.6 1/60 2-4.8 MULTIPLE CKT 1 34.6/40.0 4.6
49/56 56/60
7.2/9.6 1/60 2-4.8 MULTIPLE CKT 2 34.6/40.0 0
44/50 56/60
7.2/9.6 1/60 2-4.8 MULTIPLE CKT 3 34.6/40.0 0
44/50 56/60
RXBH-1724A07C 5.4/7.2 3/60 3-2.4 SINGLE 15.0/17.3 4.6
25/28 25/30
RXBH-1724A10C 7.2/9.6 3/60 3-3.2 SINGLE 20.0/23.1 4.6
31/35 35/35
RXBH-1724A15C 10.8/14.4 3/60 3-4.8 SINGLE 30.0/34.6 4.6
44/49 45/50
RXBH-1724A18C 12.8/17.0 3/60 3-2.84 SINGLE 35.6-41.0 4.6
51/57 60/60
RXBH-24A20C* 14.4/19.2 3/60 3-3.2 SINGLE 40.0-46.2 4.6
56/64 60/70
RXBH-24A20C
7.2/9.6 3/60 3-3.2 MULTIPLE CKT 1 20.0/23.1 4.6
31/35 35/35
7.2/9.6 3/60 3-3.2 MULTIPLE CKT 2 20.0/23.1 0
25/29 25/30
RXBH-24A25C* 18.0/24.0 3/60 6-4.0 SINGLE 50.0/57.8 4.6
69/78 70/80
RXBH-24A25C
9.0/12.0 3/60 3-4.0 MULTIPLE CKT 1 25.0/28.9 4.6
37/42 40/45
9.0/12.0 3/60 3-4.0 MULTIPLE CKT 2 25.0/28.9 0
32/37 35/40
RXBH-24A30C*
(5-ton only)
21.6/28.8 3/60 6-4.8 SINGLE 60.0/69.4 4.6 81/93 90/100
RXBH-24A30C
(5-ton only)
10.8/14.4 3/60 3-4.8 MULTIPLE CKT 1 30.0/34.7 4.6
44/50 45/50
10.8/14.4 3/60 3-4.8 MULTIPLE CKT 2 30.0/34.7 0
38/44 40/45
• ? Heater Kit Connection Type A = Breaker B = Terminal Block C = Pullout Disconnect
D Voltage = 480 Volts.
*Values only. No single point kit available.
NOTES:
• Electric heater BTUH - (heater watts + motor watts) x 3.414 (see airflow table for motor watts.)
• Supply circuit protective devices may be fuses or “HACR” type circuit breakers.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• Largest motor load is included in single circuit or circuit 1 of multiple circuits.
• Heater loads are balanced on 3 phase models with 3 or 6 heaters only.
• No electrical heating elements are permitted to be used with A voltage (115V) air handler.
• J voltage (208/240V) single phase air handler is designed to be used with single or three phase
208/240V volt electric heaters. In the case of connecting 3 phase power to air handler terminal block
without the heater, bring only two leads to terminal block, cap, insulate and fully secure the third lead.
• Do not use 480V electrical heaters on 208/240V air handlers.
• If the kit is listed under both single and multiple circuits, the kit is shipped from factory as multiple
circuits. For single phase application, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be used to convert
multiple circuits to a single supply circuit. Refer to Accessory Section for details.
[ ] Designates Metric Conversions
Electrical Data – With Electric Heat
Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the following table is recommended for all
auxiliary heating requirements.