Specification Sheet
Air
Airflow Performance Data
RHML Series
10
Model
No.
RHML
Nominal
Cooling
Capacity
Tons
Motor
Speed
From
Factory
Manufacturer
Recommended
Air-Flow Range
(Min/Max) CFM
Blower Size/
Motor
HP
# of Speeds
Y1, Y2
Speed
Motor
Speed
X-13 Wet Coil No Filter CFM Air Delivery/RPM/Watts-230 Volts
External Static Pressure—Inches W.C. [kPa]
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10]
0.5 [.12] 0.6 [.15]
0.7 [.17] 0.8 [.20]
0.9 [.22] 1.0 [.25]
-4824
No Heater
4.0
Y1 Tap 4
Y2 Tap 5
Y1=702/1271 CFM
[331/599] L/s
Y2=992/1673 CFM
[468/789] L/s
11X11
3/4 hp 5 speed
Y1
Low Static
Tap 2
CFM
1196
1046 894
819
702
—
—
— —
—
RPM
563
580 598 643
696 —
— — —
—
Watts 133 133 134 135 136
—
— — — —
Y2
Low Static
Tap 3
CFM
1517
1461
1405 1347 1297 1247
1195
1144 1068 992
RPM 670
704 735
767 799 832
867 894
940 984
Watts
251
265 277 287 296
310
322 335 351 365
Y1
High Static
Tap 4
CFM 1271 1151 1095 1039 968 883 813 745 — —
RPM
586
610 650
691 723 774
812 841
— —
Watts 164
157 168 180
186 198
211 219 —
—
Y2
High Static
Tap 5
CFM 1673 1625 1576 1527 1476
1431
1381 1339 1289 1239
RPM
726
756
783 815 841 870
901
929 956 983
Watts
329
341 355 370
378 389
405 415 427
441
-4824
With 25 kW
Heater
4.0
Y1 Tap 4
Y2 Tap 5
Y1=672/1241 CFM
[314/582] L/s
Y2=962/1643 CFM
[451/772] L/s
11X11
3/4 hp 5 speed
Y1
Low Static
Tap 2
CFM
1166
1016 864 789 672
—
— — — —
RPM
588
605 623 668 721
—
— — — —
Watts 138 138 139 140 141 — — — — —
Y2
Low Static
Tap 3
CFM
1487
1431 1375
1317 1267 1217
1165 1114
1038 962
RPM 695 729 760 792 824 857 892 919 965 1009
Watts 256 270 282 292 301 315 327 340 356 370
Y1
High Static
Tap 4
CFM
1241
1121
1065 1009 938 853
783
715 — —
RPM
611
635 675 716
748 799
837 866 —
—
Watts 169 162 173 185 191 203 216 224 — —
Y2
High Static
Tap 5
CFM
1643
1595
1546 1497 1446 1401
1351
1309 1259 1209
RPM
751
781
808 840 866 895
926
954 981 1008
Watts 334
346
360
375 383
394
410
420 432 446
Airflow Performance Data
Notes: • All 208/240V PSC motors have voltage taps for 208 and 240 volts.
• All 208/240V PSC motors are shipped on high speed and 240 volts.
• If the application external static is less than 0.5" WC, adjust the motor speed to the low static speed as described below:
• Unplug the black motor wire off the relay on the control board and plug in the red motor wire.
• Replace the cap on the black motor wire.
• Voltage change (208/240V motors):
• Move the orange lead to transformer 208V tap from 240V tap. Replace the wire cap on 240V tap.
• Unplug the purple motor wire off the transformer and plug in the yellow motor wire.
• Replace the cap on the purple motor wire.
• The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed.
Approximate Airflow = Airflow without heater - (Airflow without heater - Airflow with maximum heater) x (N kW/maximum heater kW)
[ ] Designates Metric Conversions