Specification Sheet

Air
Airflow Performance Data
RHLL Series
9
External Static Pressure—Inches W.C. [kPa]
PSC CFM [L/s] Air Delivery/RPM/Watts—115/208/240 Volts
RPM 637
Blower Size/
Motor
HP [W]
# of Speed
692
Tonnage
Application
746
Manufacturer
Recommended
Air-Flow Range
(Min/Max) CFM
Motor
Speed
801 847
Watts 130 142 153 165 176
10x10
3/4 HP [559]
5 Speed
3
CFM 1103 1059 1000
RPM
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
917 957 1001
Model
No.
RHLL
-3821
No Heater
-3821
with 18 kW
Heater
-3821
No Heater
-3821
with 18 kW
Heater
2.5 Ton
854/1103 CFM
[403/521 L/s]
2
CFM 1073 [506] 1016 [479] 963 [454] 906 [428] 854 [403]
Watts 262 271 285
RPM 678 734 791 844 883
Watts 141 155 158 171 182
10x10
3/4 HP [559]
5 Speed
3
CFM 1016 961 904
RPM 939 968 1015
2.5 Ton
828/1016 CFM
[391/479 L/s]
2
CFM 1044 [493] 988 [466] 936 [442] 880 [415] 828 [391]
Watts 233 243 265
RPM 724 761 814 868 900
Watts 198 208 222 237 245
10x10
3/4 HP [559]
5 Speed
5
CFM 1288 1244 1200
RPM 974 1012 1044
3 Ton
1070/1288 CFM
[505/608 L/s]
4
CFM 1264 [597] 1223 [577] 1171 [553] 1112 [525] 1070 [505]
Watts 345 362 371
RPM 759 794 845 915 933
Watts 219 215 227 251 261
10x10
3/4 HP [559]
5 Speed
5
CFM 1257 1213 1169
RPM 1020 1023 1054
3 Ton
1042/1257 CFM
[492/593 L/s]
4
CFM 1233 [582] 1193 [563] 1142 [539] 1084 [512] 1042 [492]
Watts 355 368 376
Motor
Speed
From
Factory
4
4
4
4
Notes: X-13 (ECM) motor speed changes.
All X-13 (ECM) motors have 5 speed tabs. Speed tab 1 is for continuous fan. Speed tab 2 (low static) and Speed tab 3 (high static) are for lower tonnage. Speed tab 4
(low static) and Speed tab 5 (high static) are for higher tonnage.
X-13 (ECM) air handlers are always shipped from factory at Speed tab 5, except for -4824, which is set at Speed tab 3. For instance, RHLL-HM2417JA is always
shipped at high static 2-ton airflow (Speed tab 5). To change to 1.5-ton airflow, move the blue wire to Speed tab 2 or 3 on the X-13 (ECM) motor.
The low static Speed tab 2 (lower tonnage) and 4 (higher tonnage) are used for external static below 0.5" WC. The high static Speed tab 3 (lower tonnage) and 5
(higher tonnage) are used for external static exceeding 0.5" WC. Move the blue wire to the appropriate Speed tab as required by the application needs.
The airflow for continuous fan (Speed tab 1) is always set at 50% of the Speed tab 4.
The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed.
Approximate Airflow = Airflow without heater – (Airflow without heater – Airflow with maximum heater) x (N kW/maximum heater kW)
[ ] Designates Metric Conversions
115V/208V/240V/480V Airflow Performance Data—RHLL (X-13 (ECM) Motor) (con’t.)