Specification Sheet

Air
Electrical Data
RHLL Series
12
Model
RHLL
Voltage
Application
Phase*
Hertz HP [W] RPM Speeds
Circuit
Amps.
Minimum
Circuit
Ampacity
Maximum
Circuit
Protector
3617/3621 1/2 [373] 300-1100 4 2.8 4.0 15
2417
208/240 1 & 3 60
1/3 [249] 300-1100 4 1.6 2.0 15
3821/4821/4824 3/4 [559] 300-1100 4 4.0 5.0 15
6024 3/4 [559] 300-1100 4 4.6 6.0 15
6024 3/4 [559] 300-1100 4 8.4 11.0 15
2417
115
1 60
1/3 [249] 300-1100 4 4.8 6.0 15
3821/4821/4824 3/4 [559] 300-1100 4 8.4 11.0 15
6024 3/4 [559] 300-1100 4 3.2 4.0 15480 3 60
Electrical Data – Blower Motor Only – No Electric Heat
* Blower motors are all single phase motors.
[ ] Designates Metric Conversions