Specification Sheet
11
External Static Pressure—Inches W.C. [kPa]
X-13 CFM [L/s] Air Delivery/RPM/Watts—115/208/240 Volts
Blower Size/
Motor
HP [W]
# of Speed
Tonnage
Application
Manufacturer
Recommended
Air-Flow Range
(Min/Max) CFM
Motor
Speed
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
Model
No.
RHLL
-6024
No Heater
-6024
with 30 kW
Heater
4
RPM 712 749 787 815 856 — —
Watts 389 409 419 432 459 — —
11x11
3/4 HP [559]
5 Speed
4
CFM — — — — 1905 [899] 1866 [881] 1832 [865]
RPM — — — — 894 924 950
5 Ton
1739/1905 CFM
[821/899 L/s]
CFM 1902 [898] 1862 [879] 1809 [854] 1781 [840] 1739 [821] — —
Watts — — — — 565 570 592
RPM 750 790 810 850 880 — —
Watts 410 420 430 455 479 — —
11x11
3/4 HP [559]
5 Speed
CFM — — — — 1865 [880] 1826 [862] 1792 [846]
RPM — — — — 920 945 970
5 Ton
1699/1865 CFM
[802/880 L/s]
CFM 1862 [879] 1822 [860] 1769 [835] 1741 [822] 1699 [802] — —
Watts — — — — 565 587 610
5
5
Motor
Speed
From
Factory
5
5
115V/208V/240V/480V Airflow Performance Data—RHLL (X-13 (ECM) Motor) (con’t.)
Notes: • All 208/240V PSC motors have voltage taps for 208 and 240 volts.
• All 208/240V PSC motors are shipped on high speed and 240 volts.
• If the application external static is less than 0.5" WC, adjust the motor speed to the low static speed as described below:
• Unplug the black motor wire off the relay on the control board and plug in the red motor wire.
• Replace the cap on the black motor wire.
• Voltage change (208/240V motors):
• Move the orange lead to transformer 208V tap from 240V tap. Replace the wire cap on 240V tap.
• Unplug the purple motor wire off the transformer and plug in the yellow motor wire.
• Replace the cap on the purple motor wire.
• The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed.
Approximate Airflow = Airflow without heater - (Airflow without heater - Airflow with maximum heater) x (N kW/maximum heater kW)
[    ] Designates Metric Conversions
Air
Airflow Performance Data
RHLL Series