Specification Sheet
Air
Electrical Data
RH1V/RH2V Series
14
Air Handler
Model
RH2V
Heater Model No.
Heater kW
(208/240V)
PH/HZ
No. Elements
kW Per
Type Supply
Circuit Single
Circuit Multiple
Circuit
Amps.
Motor
Ampacity
Minimum
Circuit
Ampacity
Maximum
Circuit
Protection
6024HT
RXBH-1724?07J 5.4/7.2 1/60 2 - 3.6 SINGLE
26.0/30.0 4.9 39/44 40/45
RXBH-1724?10J 7.2/9.6 1/60 2 - 4.8 SINGLE
34.6/40.0 4.9 50/57 50/60
RXBH-1724A15J 10.8/14.4 1/60 3-4.8 SINGLE
51.9/60.0 4.9 71/82 80/90
RXBH-1724A15J
3.6/4.8 1/60 1 - 4.8 MULTIPLE CKT 1
17.3/20.0 4.9 28/32 30/35
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
RXBH-1724A18J 12.8/17 1/60 3-5.68 SINGLE
61.6/70.8 4.9 84/95 90/100
RXBH-1724A18J
4.3/5.7 1/60 1 - 5.68 MULTIPLE CKT 1
20.5/23.6 4.9 32/36 35/40
8.7/11.3 1/60 2 - 5.86 MULTIPLE CKT 2
41.1/47.2 0.0 52/59 60/60
RXBH-24A20J 14.4/19.2 1/60 4-4.8 SINGLE
69.2/80 4.9 93/107 100/110
RXBH-24A20J
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 1
34.6/40.0 4.9 50/57 50/60
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
RXBH-24A25J 18.0/24.0 1/60 6-4.0 SINGLE
86.4/99.9 4.9 115/131 125/150
RXBH-24A25J
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 1
28.8/33.3 4.9 43/48 45/50
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 2
28.8/33.3 0.0 36/42 40/45
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 3
28.8/33.3 0.0 36/42 40/45
RXBH-24A20J 14.4/19.2 1/60 4-4.8 SINGLE
69.2/80 4.9 93/107 100/110
RXBH-24A20J
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 1
34.6/40.0 4.9 50/57 50/60
7.2/9.6 1/60 2 - 4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
RXBH-24A25J 18.0/24.0 1/60 6-4.0 SINGLE
86.4/99.9 4.9 115/131 125/150
RXBH-24A25J
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 1
28.8/33.3 4.9 43/48 45/50
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 2
28.8/33.3 0.0 36/42 40/45
6.0/8.0 1/60 2-4.0 MULTIPLE CKT 3
28.8/33.3 0.0 36/42 40/45
RXBH-24A30J 21.6/28.8 1/60 6-4.8 SINGLE
103.8/120 4.9 136/156 150/175
RXBH-24A30J
7.2/9.6 1/60 2-4.8 MULTIPLE CKT 1
34.6/40.0 4.9 50/57 50/60
7.2/9.6 1/60 2-4.8 MULTIPLE CKT 2
34.6/40.0 0.0 44/50 45/50
7.2/9.6 1/60 2-4.8 MULTIPLE CKT 3
34.6/40.0 0.0 44/50 45/50
Electrical Data – With Electric Heat RH2V (con’t.)
Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the following table is recommended for all
auxiliary heating requirements.
• Supply circuit protective devices may be fuses or “HACR” type circuit breakers.
• Largest motor load is included in single circuit and multiple circuit 1.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• J Voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3-phase power to the air handler terminal block
without the heater, bring only two leads to the terminal block cap, insulate and fully secure the third lead.
[ ] Designates Metric Conversions