Instructions / Assembly
The manufacturer’s warranty does not cover any damage or defect 
caused by installation, or attachment, or use of any special attach-
ment such as energy saving devices (other than those authorized 
by the manufacturer) into,  onto, or in conjunction with the water 
heater. The use of such unauthorized devices may shorten the life 
of the water heater and may endanger life and property. The manu-
facturer disclaims any responsibility for such loss or injury result-
ing from the use of such unauthorized devices.
1.  INSPECT SHIPMENT — for possible damage. The manufacturer’s 
responsibility ceases upon delivery of goods to the carrier in good 
condition. Any claims for damage, shortage in shipments, or non 
delivery must be filed immediately against carrier by consignee.
2.  DRAFT HOOD — The combination  draft hood - flue damper as-
sembly designed for and shipped with this water heater must be 
installed, without alteration, directly on the flue outlet collar. DO 
NOT   substitute any other size or type of draft hood.
  Before proceeding with installation, verify that the part number on 
the draft hood - flue damper assembly matches that called for on 
label near connector. If not, see your distributor or the store from 
where the water heater was purchased.
A.) Place the draft hood - flue damper assembly on the flue outlet of 
the water heater with the drive motor to the left front. Rotate as 
necessary to position where the plug on the end of the wire har-
ness can freely engage in the receptacle of the drive motor.
B.) Mark a spot on top pan through the hole in support bracket at the 
rear of the drive motor. (Refer to Figure 3.)
C.) Remove  the draft hood - flue  damper assembly  and drill a hole 
through the spot for securing it with sheet metal screw.
D.) Reinstall the draft hood - flue damper assembly and secure it with 
a sheet metal screw through the support bracket. Also install three 
(3) 3/8”(.95 cm) maximum length self drilling screws (supplied with 
Damper Assembly) into holes located around the base of Damper 
Assembly. (Refer to Figure 3.)
E.) Electrical connections to the drive motor are made with a plug that 
is polarized to insure correct insertion. The drive motor receptacle 
is external to the casing for easy access. (Refer to Figure 3.)
3.  VENTING — The responsibility for providing a vent of adequate capacity 
and in good usable condition is that of the installing contractor. If the water 
heater is being installed as a replacement for an existing water heater, a 
thorough inspection of the existing venting system must be performed prior 
to any installation work.  Verify that the correct materials and clearances 
have been used for the installation.  There is a limit to the Btu/h capacity of 
any given vent or chimney style and height. For installations in the United 
States, capacity tables are printed in Appendix “G” of the National Fuel 
Gas Code (ANSI Z223.1). For installations in Canada, this information is 
contained in Appendix B of CAN/CGA B-149.1Installation Codes
  As an alternate method for sizing a vent connected to more than one 
appliance, the effective area of the vent shall be not less than the area of 
the largest vent connector plus 50% of the areas of additional draft hood 
outlets.
  Any horizontal run of vent connector connecting the draft hood to the 
gas vent or chimney, must have an upward slope of at least 1/4” per foot 
of length. Single wall vent connectors must be at least 6” from adjacent 
unprotected combustible surfaces. Joints of vent connectors should be 
securely fastened by sheet metal screws or other approved method. Pro-
vide support for vent, or vent connectors to keep weight off draft hood.
4.  GAS SERVICE — The inlet gas pressure to the water heater must not 
exceed 10.5” w.c. (2.6 kPa) for Natural gas and 13.0” w.c. (3.2 kPa) for 
L.P. gas. Note: The Power Assist Burner Unit uses only Natural Gas and 
should follow the guidelines stated in the previous sentence for inlet gas 
pressure. For purposes of input adjustment, the minimum inlet gas pres-
sure (with main burner on) is shown on the rating plate. Check to see if 
high or low gas pressure is present and then contact the gas company 
for correction.
  The gas line should be of adequate size to prevent undue pressure 
drop. Sizing based upon Table 1 (on pg. 14) is recommended. No 
additional allowance is necessary for an ordinary number of fittings.
   A ground joint union and manual shutoff valve should be installed 
in the gas line near the water heater so that the burner assembly 
may be easily removed. The shut-off valve must be readily acces-
sible for turning on or off. See Fig. 4 or 5 on page 6.
  A sediment trap must be installed  at the bottom of the  gas  line. 
See Fig. 4 or 5 on page 6.
5
  Large exhaust fans can lower the air pressure inside a building or 
room and interfere with proper venting and operation. Commercial 
kitchens or other locations that must maintain a high flow of ex-
haust air should have the water heater installed in a separate room 
with combustion and ventilation air supplied directly from outside 
as described above.
F.  CORROSIVE  ATMOSPHERES  — The  heater  should  not be in-
stalled near an air supply containing halogenated hydrocarbons. 
For example, the air in beauty shops, dry cleaning establishments, 
photo processing labs, and storage areas for liquid and powdered 
bleaches or swim pool chemicals often contain such hydrocarbons. 
The air there may be safe to breathe, but when it passes through 
a gas flame, corrosive elements are released that will shorten the 
life of any gas burning appliance. Propellants from common spray 
cans or gas leaks from refrigeration equipment are highly corrosive 
after passing through a flame. The limited warranty is voided when 
failure of water heater is due to a corrosive atmosphere. (Reference 
is made to the limited warranty for complete terms and conditions.) 
Introduction
Installation
WARNING
!
Figure 3. — Installing Damper / Draft Hood Assembly
Damper Mounting
Screw
3/8” Maximum Length Damper
 Mounting  Screw
Additional screws located at 90° 
intervals around Damper Base
Insert  Polarized  Plug  into  re-
ceptacle  on Drive  Motor  after 
Damper / Draft Hood Assembly 
is secured to water heater.
Note:  Damper  MUST be in open  position  when water 
heater main burner is operating










