Specification Sheet

Air
Airflow Performance Data
RHBL/RHAL Series
9
External Static Pressure-Inches W.C. [kPa]
X-13 CFM wet coil with filter and heaters
RPM 1120
Blower Size/
Motor
HP [W]
# of Speeds
1132
Motor
Speed
1136
Manufacturer
Recommended
Air-Flow Range
(Min/Max) CFM
Motor
Speed
From
Factory
1141 1146 1153 1160
Watts 294 271 266 257 239 231 214
10x6
1/3 HP [249]
2 Speed
Dual Voltage
CFM 811 [383] 785 [370] 759 [358] 726 [343] 708 [334]
RPM
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
982 1008 1026 1050 1081
RPM 1020 1035 1068 1095 1119 1138 1147
Nominal
Cooling
Capacity
Tons
2
2.5
3
1.5
Watts 198 207 206 204 211 205 189
10x6
1/3 HP [249]
2 Speed
Dual Voltage
4
977/708 CFM
[461/334 L/s]
CFM 599 [283] 578 [273] 544 [257] 509 [240] 474 [224]
5
CFM 977 [461] 930 [439] 898 [424] 850 [401]
RPM 832 875 905 935 963
801 [378] 746 [352] 687 [324]
Watts 177 186 182 188 189
RPM 886 921 958 986 1022 1053 1083
Watts 267 275 287 290 301 305 315
10x8
1/2 HP [373]
2 Speed
Dual Voltage
CFM 1053 [497] 1003 [473] 969 [457] 928 [438] 897 [423]
RPM 835 864 903 933 973
2
1170/897 CFM
[552/423 L/s]
5
CFM 1170 [552] 1127 [532] 1085 [512] 1048 [495] 1012 [478] 973 [459] 943 [445]
Watts
212 216 227 232 242
RPM 974 1006 1036 1063 1098 1120 1131
Watts 365 378 383 390 399 393 377
10x8
1/2 HP [373]
2 Speed
Dual Voltage
CFM 1208 [570] 1172 [553] 1125 [531] 1087 [513] 1049 [495]
RPM 906 938 968 1002 1030
5
1316/1049 CFM
[621/495 L/s]
5
CFM 1316 [621] 1275 [602] 1229 [580] 1191 [562] 1151 [543] 1093 [516] 1039 [490]
Watts 284 299 306 315 322
2
827/474 CFM
[390/224 L/s]
5
CFM 827 [390] 804 [379] 779 [368] 740 [349] 708 [334] 659 [311] 608 [287]
Watts
95 96 108 102 112
3
4
5
3
5
5
5
5
208V/240V Airflow Performance Data—RHBL (X-13 (ECM) Motor)
Notes: X-13 motor speed changes.
All X-13 motors have 5 speed taps. Speed tap 1 is for continuous fan. Speed tap 2 (low static) and speed tap 3 (high static) are for lower tonnage. Speed tap 4 (low
static) and speed tap 5 (high static) are for higher tonnage.
X-13 air handlers are always shipped from factory at speed tap 5. To change to 1.5-ton or 2.5-ton airflow, move the blue wire to speed tap 2 or 3 on the
X-13 motor. The low static speed tap 2 (lower tonnage) and 4 (higher tonnage) are used for external static below 0.5" WC. The high static speed tap 3 (lower tonnage)
and 5 (higher tonnage) are used for external static exceeding 0.5" WC. Move the blue wire to the appropriate speed tap as required by the application needs.
The airflow for continuous fan (speed tap 1) is 50% of the speed tap 4 airflow.
The above airflow table lists the airflow information for air handlers with maximum heater allowed for each model.
[ ] Designates Metric Conversions