Air Air Handlers RHBL/RHAL Series Rheem Air Handler RHBL- Series X-13 (ECM) Motor Efficiencies up to 16 SEER RHAL- Series PSC Motor Efficiencies up to 14.
Air Table of Contents RHBL/RHAL Series TABLE OF CONTENTS Engineering Features ......................................................................................3 Model Number Identification ............................................................................4 Dimensional Data ........................................................................................5-6 Airflow Performance Data ............................................................................7-9 Piston Sizing Chart.....
Air Engineering Features RHBL/RHAL Series Engineering Features RHBL/RHAL- Series • The most compact unit design available, all standard heat air handler models only 36" [915 mm]. • Rugged wall steel cabinet construction, designed for added strength and versatility. • 1.0" foil faced insulation for excellent thermal and sound performance. • Four leg blower motor mount. • Traditional open wire element design for heat applications.
Air Model Number Identification RHBL/RHAL Series Model Number Identification R H A L — FR 24 P J N 00 A 000 Options 417 = Float Switch Available Models at J Voltage Design Variation RHAL-FR18PJ RHAL-FR24PJ RHAL-FR30PJ RHAL-FR36PJ RHAL-FR36TJ RHBL-FR24TJ RHBL-FR36TJ Electric Heat 00 = NO HEAT 03 = 3 kW 05 = 5 kW 08 = 8 kW 10 = 10 kW Disconnect Configuration N = None B = Breaker Voltage J = 208/240/1/60 Metering P = Piston (R22 or R410A) T = TXV (R410A) Capacity 18 = 18,000 BTU/H [5.
Air Dimensional Data RHBL/RHAL Series Unit Dimensions Unit Dimensions & Weights Dimensional Data Model RHAL-18 RHAL-24 RHAL-30 RHAL-36 RHBL-24 RHBL-36 (A) Unit Width In. [mm] 211/2 [546.1] 211/2 [546.1] 241/2 [609.6] 241/2 [609.6] 211/2 [546.1] 241/2 [609.6] (B) Unit Height In. [mm] 36 [914.4] 36 [914.4] 36 [914.4] 36 [914.4] 36 [914.4] 36 [914.4] (C) Unit Depth In. [mm] 17 [431.8] 17 [431.8] 21 [533.4] 21 [533.4] 17 [431.8] 21 [533.4] (D) Return Air Opening Width In. [mm] 20 [508] 20 [508] 23 [584.
Air Dimensional Data RHBL/RHAL Series Unit Dimensions (con’t.) 11/2 & 2 TON [5.28 & 7.03 kW] MODELS [ ] Designates Metric Conversions 6 21/2 & 3 TON [8.79 & 10.
Air Airflow Performance Data RHBL/RHAL Series Airflow Performance Airflow performance data is based on cooling performance with a coil and filter in place. Select performance table for appropriate unit size, voltage and number of electric heaters to be used. Make sure external static applied to unit allows operation within the minimum and maximum limits shown in table below for both cooling and electric heat operation. For optimum blower performance, operate the unit in the .3 [8 mm] to .
Air Airflow Performance Data RHBL/RHAL Series 208V/240V Airflow Performance Data—RHAL (PSC Motor) Nominal Cooling Capacity Tons 1.5 2 2.
Air Airflow Performance Data RHBL/RHAL Series 208V/240V Airflow Performance Data—RHBL (X-13 (ECM) Motor) Nominal Cooling Capacity Tons 1.5 2 2.
Air Piston Sizing Chart RHBL/RHAL Series Piston Sizing Chart Indoor Unit Factory Piston RHAL-FR18PJ 0.047 RHAL-FR24PJ 0.053 RHAL-FR30PJ 0.061 RHAL-FR36PJ 0.065 10 SEER Rating OD Unit Nominal Tons Refrigerant Orifice Size 13 1.5 R410a 0.047 14 13 12 10 13 14 13 12 10 13 14 13 12 10 13 14 13 12 10 1.5 1.5 1.5 1.5 2 2 2 2 2 2.5 2.5 2.5 2.5 2.5 3 3 3 3 3 R410a R22 R22 R22 R410a R410a R22 R22 R22 R410a R410a R22 R22 R22 R410a R410a R22 R22 R22 0.049 0.049 0.051 0.053 0.053 0.057 0.057 0.
Air Electrical Data RHBL/RHAL Series RHAL/RHBL Electrical Data – Blower Motor Only – No Electric Heat 1.5 Minimum Circuit Ampacity 3 Maximum Circuit Protector 15 1.5 2.5 3 4 15 15 2 2.5 4 15 4 4 1.6 2.7 3 4 15 15 Model/Nominal Cooling Tons Voltage Phase Hertz HP [W] RPM Speeds Circuit Amps.
Air Accessories RHBL/RHAL Series 16.0 Accessories-Kits-Parts • Drain Pan Over Flow Switch RXHK-A01 is used to detect condensate drain blockage and will shut down the outdoor unit in order to prevent structural damage to the surrounding structures of the air handler. • Bottom Return Conversion Kit RXHK- is used to divert the return air from the factory standard front return to a bottom return.
Air Limited Warranty RHBL/RHAL Series GENERAL TERMS OF LIMITED WARRANTY* Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable periods stated, in accordance with the terms of the limited warranty. Conditional Parts (Registration Required) ..........
Air 14 Notes RHBL/RHAL Series
Air Notes RHBL/RHAL Series 15
The new degree of comfort.™ In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice. Rheem Heating, Cooling & Water Heating • P.O. Box 17010 Fort Smith, Arkansas 72917 • www.rheem.com Rheem Canada Ltd./Ltée • 125 Edgeware Road, Unit 1 Brampton, Ontario • L6Y 0P5 PRINTED IN U.S.A 12/12 QG FORM NO.