Operating instructions
7
!
WARNING: The pressure 
rating of the relief valve 
must not exceed 150 PSI, 
the maximum working 
pressure of the water heater 
as marked on the rating 
plate. 
A new combination temperature and pressure relief valve, complying with the Standard for Relief 
Valves and Automatic Gas Shut-Off Devices for Hot Water Supply Systems, ANSI Z21.22, is supplied 
and must be installed in the opening provided and marked for the purpose on the water heater. No 
valve of any type should be installed between the relief valve and the tank. Local codes shall govern the 
installation of relief valves.
Relief Valve
The BTUH rating of the relief valve must 
not be less than the input rating of the 
water heater as indicated on the rating 
label located on the front of the heater  
(1 watt=3.412 BTUH).
Connect the outlet of the relief valve  
to a suitable open drain so that the 
discharge water cannot contact live 
electrical parts or persons and to eliminate 
potential water damage. 
Piping used should be of a type approved 
for hot water distribution. The discharge 
line must be no smaller than the outlet of 
the valve and must pitch downward from 
the valve to allow complete drainage (by 
gravity) of the relief valve and discharge 
line. The end of the discharge line should 
not be threaded or concealed and should 
be protected from freezing. No valve of 
any type, restriction or reducer coupling 
should be installed in the discharge line.
To Fill the Water Heater
Make certain the drain valve is completely 
closed. 
Open the shut-off valve in the cold water 
supply line.
Open each hot water faucet slowly to 
allow the air to vent from the water  
heater and piping. 
A steady flow of water from the hot water 
faucet(s) indicates a full water heater.
!
WARNING: The tank 
must be full of water before 
heater is turned on. The 
water heater warranty does 
not cover damage or failure 
resulting from operation 
with an empty or partially 
empty tank.
Condensation
Condensation can form on the tank when 
it is first filled with water. Condensation 
might also occur with a heavy water draw 
and very cold inlet water temperature.
This condition is not unusual, and will 
disappear after the water becomes heated. 
If, however, the condensation continues, 
examine the piping and fittings for 
possible leaks.










