Specification Sheet
Coil
Model
Number
Approx.
Design
Air Flow
CFM [L/s]
Range
Face
Area
Sq. Ft.
[m
2
]
Fins-in.
Rows
Deep
Static Pressure Drop Through Wet Cooling Coil [kPa] (Inches W.C.) CFM [L/s]
600
[283]
700
[330]
800
[378]
900
[425]
1000
[472]
1100
[519]
1200
[566]
1300
[614]
1400
[661]
1500
[708]
1600
[756]
1700
[802]
1800
[850]
1900
[897]
2421
600/800
[283/378]
5.70
[0.53]
16/2
0.05
[0.01]
0.10
[0.02]
0.15
[0.04]
0.18
[0.04]
— — — — — — — — — —
HIGH EFFICIENCY COOLING COILS
2417
600/800
[283/378]
5.70
[0.53]
16/2
0.07
[0.02]
0.12
[0.03]
0.17
[0.04]
0.21
[0.05]
— — — — — — — — — —
3624
825/1175
[389/555]
9.98
[0.93]
14/3 — —
0.07
[0.02]
0.09
[0.02]
0.11
[0.03]
0.14
[0.03]
0.16
[0.04]
— — — — — — —
4821
1200/1800
[566/850]
5.33
[0.50]
14/4 — — — — — —
0.21
[0.05]
0.23
[.059]
0.25
[.063]
0.30
[.076]
0.32
[.081]
0.37
[0.94]
—
—
6024
1050/1700
[496/802]
9.98
[0.93]
14/3 — — — —
0.11
[0.03]
0.14
[0.03]
0.16
[0.04]
0.19
[0.05]
0.21
[0.05]
0.24
[0.06]
0.27
[0.07]
0.31
[0.08]
— —
4824
1000/1600
[472/755]
9.98
[0.93]
14/3 — — — —
0.11
[0.03]
0.14
[0.03]
0.16
[0.04]
0.19
[0.05]
0.21
[0.05]
0.24
[0.06]
0.27
[0.07]
— — —
6021
1400/1900
[660/897]
5.83
[0.55]
15/4 — — — — — — — —
0.26
[.066]
0.30
[0.76]
0.32
[.081]
0.36
[.092]
0.40
[.100]
0.44
[.112]
3
Model Number Identification
Table 1: Coil Specifications/Airflow Pressure Drop
NOTE: Represents Coil-Only Airflow Ratings
[ ] Designates Metric Conversions
Available Models of RCFN Coils
RCFN-HU2417AU RCFN-HU6024TU
RCFN-HU2421AU RCFN-HM2417AC
RCFN-HU3624AU RCFN-HM2421AC
RCFN-HU4824AU RCFN-HM3624AC
RCFN-HU6024AU RCFN-HM4824AC
RCFN-HU2417CU RCFN-HM6024AC
RCFN-HU2421CU RCFN-HM2417CC
RCFN-HU3624CU RCFN-HM2421CC
RCFN-HU4824CU RCFN-HM3624CC
RCFN-HU6024CU RCFN-HM4824CC
RCFN-HU2417TU RCFN-HM6024CC
RCFN-HU2421TU RCFN-AM4821AC
RCFN-HU3624TU RCFN-AM6021AC
RCFN-HU4824TU
Air
Model I.D./Coil Specifications
RCFN Series
RCFN—HM2414AC
Gas/Oil Furnace Coil
C = Cased
U = Uncased
Design Variation
A = 1st Design
C = Coil Change
T = Tin plated copper tubing in finned area
Coil Size
17 = 17.5" [431.8 mm]
21 = 21" [533.4 mm]
24 = 24.5" [609.6 mm]
Nominal Capacity
24 = 24,000 BTU/HR
[7.03 kW]
36 = 36,000 BTU/HR
[10.55 kW]
48 = 42,000 to 48,000 BTU/HR
[12.31 to 14.06 kW]
60 = 60,000 BTU/HR
[17.58 kW]
Cased Coil Airflow:
HM = A/C or Heat Pump, Multi-Position
AM = A/C, Multi-Position
Uncased Coil Airflow:
HU = A/C or Heat Pump, Upflow/Downflow
Refrigerant/Metering Device
N = R-410A (18 SEER)
F = Product Generation
Classification
C = Coil
Rheem