Operating instructions
62 
COMMISSIONING 
All water heaters are tested and adjusted before dispatch from the factory, however further adjustments may 
become necessary because of local conditions. 
TO TURN ON THE WATER HEATER 
•  Open all of the hot taps in the house (don’t forget the shower). 
•  Open the cold water isolation valve fully at the inlet to the water heater. 
Air will be forced out of the taps. 
•  Close each tap as water flows freely from it. 
•  Check the pipe work for leaks. 
•  Open the gas isolation valve fully. 
•  Check the gas pipe work for leaks. 
•  Plug in the water heater at the power outlet and switch on the electrical supply. 
•  Turn on a controller, if one is fitted, by pressing the on / off button. 
The light in the on / off button and the ACTIVE light will both glow. 
•  Open a hot tap. 
The water heater will operate automatically. 
•  Check to ensure the flow from each connected hot tap is sufficient to operate the water heater. 
The minimum operating flow rate for all models is 2.0 litres per minute. 
•  Check and if required adjust the preset outlet temperature setting of the water heater. 
Refer to “Preset Outlet Temperature Setting” on page 66. 
The automatic water governor incorporated in the water heater is not adjustable. 
To complete the installation, it is necessary to check the gas supply pressure at the inlet to the water heater 
(refer to “Gas Inlet Pressure” on page 62), the minimum test point pressure and the maximum test point 
pressure (refer to “Burner Gas Pressure” on page 64). 
Upon completion and testing of the installation, ensure the controller(s) is turned off (if fitted). Explain to the 
householder or a responsible officer the functions and operation of the water heater and the controllers (if 
fitted). 
 Warning: Upon completion of the installation and commissioning of the water heater, leave this guide 
with the householder or a responsible officer. DO NOT
 leave this guide inside of the cover of the water 
heater, as it may interfere with the safe operation of the water heater or ignite when the water heater is 
turned on. 
GAS INLET PRESSURE 
IMPORTANT - CHECK 
the gas supply pressure at the inlet to the water heater with the water heater and all 
other gas burning appliances in the premises operating (burners alight). The minimum gas supply pressure 
is: 
  Natural Gas  1.13 kPa  Propane / LPG  2.75 kPa 
If this minimum cannot be achieved, it may indicate the meter or the gas line to the water heater is 
undersized. It is important to ensure that an adequate gas supply pressure is available to the water heater 
when other gas burning appliances, on the same gas supply, are operating. 