Operating instructions

INSTALLATION – WATER HEATER
36
WATER HEATER LOCATION
The water heater should be installed close to the most frequently used outlet and its position chosen with
safety and service in mind. If this water heater is part of a solar water heater system, it should also be
installed close to the solar storage tank. Make sure people (particularly children) will not touch the flue
terminal. The flue terminal and air inlet must be clear of obstructions and shrubbery.
Clearance must be allowed for servicing of the water heater. The water heater must be accessible without
the use of a ladder or scaffold. Make sure the entire front panel can be removed for service. You must be
able to read the information on the rating plate. Remember you may have to take the entire water heater out
later for servicing.
This water heater must be installed vertically upright with
the water, gas and power connections on the underside,
pointing toward the ground. The back of the water heater
can be either against a wall or supported by a frame. The
water heater must be secured to the wall or frame using
either the screws provided or other mounting screws
suitable for the application, two each at the top and bottom
of the unit (refer to page 43 for mounting hole positions).
For a single water heater installation, refer to the typical
installation diagram on page 45.
For a dual water heater installation using the Ez-Link
system, refer to “Ez-Link System Dual Installation” on
page 49 and the typical installation diagram on page 52.
The water heater must not be installed in an area with a corrosive atmosphere where chemicals are stored or
where aerosol propellants are released. Remember the air may be safe to breathe, but when it goes through
a flame, chemical changes take place which may attack the water heater.
A secondary flue is not required. The water heater must not be installed indoors or in a confined space.
The water heater must be located to ensure that the location of the flue terminal complies with the
requirements of AS 5601 or AS/NZS 5601.1 or NZS 5261, as applicable under local regulations. As a guide
the following requirements are extracted from the Gas Installations Standard. The distances are measured
along the wall behind the water heater.
At least 300 mm between the top of the flue terminal
and the eaves.
At least 300 mm between the flue terminal and the
edge of any opening into the building, such as an
openable door or window, measured horizontally*.
At least 1500 mm between the top of the flue terminal
and the edge of any opening into the building, such as
an openable window, measured vertically.
At least 300 mm between the flue terminal and a
return wall or external corner, measured horizontally*.
At least 1500 mm between the flue terminal and any
opening into a building, in the direction of the flue
discharge.
At least 500 mm between the flue terminal and a fence, wall or other obstruction, in the direction of the
flue discharge.
Note: * If these horizontal distances cannot be achieved, AS/NZS 5601.1 states an equivalent horizontal
distance measured diagonally from the nearest discharge point of the flue terminal to the opening may be
deemed to comply. Check with the local regulator.