INSTALLATION 
24 
TANK WATER SUPPLY 
If the  water heater is  supplied with  water from a tank  supply and  a pressure 
pump system  is  not  installed,  then  the  bottom  of  the  supply tank must be  at 
least 1 m above the highest point of the hot water plumbing system, including 
the water heater. Care must be taken to avoid air locks. The cold water line to 
the  water  heater  should  be  adequately  sized  and  fitted  with  a  full  flow  gate 
valve or ball valve. 
HOT WATER DELIVERY 
This water heater can deliver water at temperatures which can cause scalding. 
It is necessary and we recommend that a temperature limiting device be fitted 
between  a  Rheemglas  or  Optima  water  heater  and  hot  water  outlets  in  any 
ablution and public areas such as a bathroom, ensuite or public amenities, to 
reduce the risk of scalding. The installing plumber may have a legal obligation 
to  ensure  the  installation  of  this  water  heater  meets  the  delivery  water 
temperature  requirements  of  AS/NZS 3500.4  so  that  scalding  water 
temperatures  are  not  delivered to  a bathroom,  ensuite  or  other  ablution  or 
public area. 
Where a temperature limiting device is installed adjacent to the water heater, 
the cold water line to the temperature limiting device can be branched off the 
cold water line either before or after the isolation valve, pressure limiting valve 
and non  return valve  to the water  heater.  If an expansion control  valve is 
required, it must always be installed after the non return valve and be the last 
valve prior to the water heater. 
If a pressure limiting valve is installed on the cold water line to the water heater 
and the cold water line to a temperature limiting device branches off before this 
valve or from another cold water line in the premises, then a pressure limiting 
valve  of  an  equal  pressure  setting may  be  required  prior to  the  temperature 
limiting device. 
LEGEND
Two Temperature Zones Using a Temperature Limiting Device 