Specifications

TM016 Rheem Gas Permanent Pilot Service Instructions
D.O.I: 01/2006
This document is stored and maintained electronically by Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”.
25
Fault Finding Chart 4
NO
YES
YES
Has
the usage pattern
changed recently? i.e.
additional appliances or
people using hot
water
Recommend a water heater of
sufficient capacity to meet customers
needs
YES
NO
NO
Recommend a hot water usage
pattern that will suit the water heaters
capacity and the customers needs
YES
NO
Repair any leaks.
Isolate crossed connections
YES
NO
Are
there any
plumbing leaks,
crossed connections
or dripping
taps?
Is
the T&PR
valve continuously
discharging
water?
Is the
water heater of
sufficient size for the
customers
needs?
Is the
water heater sized
as recommended in
the Rheem sizing
guide?
Is
the flue baffle
fitted?
Follow diagnostic flow
chart 2 to confirm main burner
operation is correct
Main
burner operation
is correct?
Rectify main burner fault identified in
diagnostic flow chart 2
NO
Check inlet diffuser is not restricted,
missing or damaged.
Check dip tube is not missing,
broken or incorrectly fitted
YES
Replace the baffleNO
Replace the gas control
NO
4
3.1
Does
the water
temperature at the
outlet correspond with
the thermostat
setting?
Is a
tempering valve
fitted?
YES
4.1
Is the
model a Rheem
Plus?
NO
YES
YES
NO
4.2
YES