Specification Sheet
Air
Electrical Data
RHPL Series
9
Air Handler
Cabinet Size/
Cooling
Capacity
Manufacturer
Model Number
Type Supply
Circuit
Voltage PH/HZ Heater kW Heater AMPS
Maximum
Circuit
Protection
Motor
Ampacity
Minimum
Circuit
Ampacity
24" / HM6024
RXBH-24?05J Single 208/240 1/60 3.6/4.8 17.3/20.0 4.9 30/35 28/32
RXBH-24?07J Single 208/240 1/60 5.4/7.2 26.0/30.0 4.9 40/45 39/44
RXBH-24?10J Single 208/240 1/60 7.2/9.6 34.6/40.0 4.9 50/60 50/57
RXBH-24?15J
Single 208/240 1/60 10.8/14.4 51.9/60.0 4.9 80/90 72/82
MULTI.CKT 1 208/240 1/60 3.6/4.8 17.3/20.0 4.9 30/35 28/32
MULTI.CKT 2 208/240 1/60 7.2/9.6 34.6/40.0 0 45/50 44/50
RXBH-24?18J
Single 208/240 1/60 12.8/17 61.6/70.8 4.9 90/100 84/95
MULTI.CKT 1 208/240 1/60 6.4/8.5 30.8/35.4 4.9 45/60 45/51
MULTI.CKT 2 208/240 1/60 6.4/8.5 30.8/35.4 0 40/45 39/45
RXBH-24?20J
Single 208/240 1/60 14.4/19.2 69.2/80.0 4.9 100/110 93/107
MULTI.CKT 1 208/240 1/60 7.2/9.6 34.6/40.0 4.9 50/60 50/57
MULTI.CKT 2 208/240 1/60 7.2/9.6 34.6/40.0 0 45/50 44/50
RXBH-24?25J
Single 208/240 1/60 18.0/24.0 87.0/99.9 4.9 125/150 115/132
MULTI.CKT 1 208/240 1/60 6.0/8.0 29.0/33.3 4.9 45/50 43/48
MULTI.CKT 2 208/240 1/60 6.0/8.0 29.0/33.3 0 40/45 37/42
MULTI.CKT 3 208/240 1/60 6.0/8.0 29.0/33.3 0 40/45 37/42
RXBH-24?30J
Single 208/240 1/60 21.8/28.8 103.8/120 4.9 135/168 150/175
MULTI.CKT 1 208/240 1/60 7.2/9.6 34.8/40.0 4.9 49/56 50/60
MULTI.CKT 2 208/240 1/60 7.2/9.6 34.8/40.0 0 44/50 45/50
MULTI.CKT 3 208/240 1/60 7.2/9.5 34.8/40.0 0 44/50 45/50
Electrical Data – With Electric Heat (Cont.)
Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the following table is recommended for all
auxiliary heating requirements.
• Supply circuit protective devices may be fuses or “HACR” type circuit breakers.
• Largest motor load is included in single circuit and multiple circuit 1.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• J Voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3-phase power to the air handler terminal block
without the heater, bring only two leads to the terminal block cap, insulate and fully secure the third lead.
? Heater Kit Connection Type A = Breaker B = Terminal Block C = Pullout Disconnect
[ ] Designates Metric Conversions