Specification Sheet

Air
Electrical Wiring
RHPL Series
10
Electrical Wiring
Power Wiring
• Field wiring must comply with the National Electrical Code
(C.E.C. in Canada) and any applicable local ordinance.
• Supply wiring must be 75°C minimum copper conductors only.
• See electrical data for product Ampacity rating and Circuit
Protector requirement.
Grounding
• This product must be sufficiently grounded in accordance with
National Electrical Code (C.E.C. in Canada) and any applicable
local ordinance.
• A grounding lug is provided.
RXHF-
Accessories
Auxiliary Horizontal Overflow Pan Accessory RXBM-
Combustible Floor Base RXHB-
Jumper Bar Kit 3 Ckt. to 1 Ckt. RXBJ-A31 is used to convert
single phase multiple three circuit units to a single supply
circuit. Kit includes cover and screw for line side terminals.
Jumper Bar Kit 2 Ckt. to 1 Ckt. RXBJ-A21 is used to convert
single phase multiple two circuit units to a single supply circuit.
Kit includes cover and screw for line side terminals.
Note: No jumper bar kit is available to convert three phase
multiple two circuit units to a single supply circuit.
Auxiliary Electric Heater Kits RXBH-
Heater Kits include circuit breakers which meet UL and cUL
requirements for service disconnect. See the Electric Heat
Electrical Data in this specification sheet for specific Heater Kit
Model numbers.
External Filter Rack RXHF-B17, B21, B24
*Accommodates 1" filter
21
24
RXHB-21
RXHB-24
Model Cabinet Size
Combustible Floor
Base Model Number
Nominal Cooling
Capacity-Tons
Auxiliary Horizontal Overflow Pan
Accessory Model Number
1
1
/2 - 3
RXBM-AC48
3
1
/2 - 5 RXBM-AC61
RXHF-B
B
A
B
A
1
1
/2
[38 mm]
External Filter Base RXHF-
*Accommodates 1" or 2" filter
[ ] Designates Metric Conversions
Model Cabinet Size Filter Size In. [mm]
21 20 x 20 [508 x 508]
Part Number*
RXHF-21
RXHF-2424 25 x 20 [635 x 508] 22.70
19.20
A
25.5
21.0
B
Model Cabinet Size Part Number*
RXHF-B21
Filter Size In. [mm]
RXHF-B24
24 25 x 20 [635 x 508]
21
20 x 20 [508 x 508]
A
20.40
25.00
B
20.77
21.04