Gas Supply
Table 3 - Pipe-Sizing - Natural Gas 
Schedule 40 Metallic Pipe (Black Iron)
Inlet System Pressure: Less than 2 PSI (55 inches W.C.)
Allowable Pressure Drop: 0.5 inches W.C.
Specic Gravity : 0.60
(Capacity in cubic feet per hour)
Length Pipe Size (Inches)
½ ¾ 1 1¼ 1½
10 172 360 678 1390 2090
20 118 247 466 957 1430
30 95 199 374 768 1150
40 81 170 320 657 985
50 72 151 284 583 873
60 65 137 257 528 791
70 60 126 237 486 728
80 56 117 220 452 677
90 52 110 207 424 635
100 50 104 195 400 600
Information in this chart obtained from NFPA 54, ANSI Z223.1 - 2012 Table 6.2(b)
Table 4 - Pipe-Sizing - Natural Gas 
Schedule 40 Metallic Pipe (Black Iron)
Inlet System Pressure: 8.0 inches W.C. or greater, but Less than 2 PSI (55 
inches W.C.)
Allowable Pressure Drop: 3.0 inches W.C.
Specic Gravity : 0.60
(Capacity in cubic feet per hour)
Length Pipe Size (Inches)
½ ¾ 1 1¼ 1½
10  454   949   1,787   3,669   5,497 
20  312   652   1,228   2,522   3,778 
30  250   524   986   2,025   3,778 
40  214   448   844   1,733   2,597 
50  190   387   748   1,536   2,302 
60  172   360   678   1,392   2,085 
70  158   331   624   1,280   1,919 
80  147   308   580   1,191   1,785 
90  138   289   544   1,118   1,675 
100  131   273   514   1,056   1,582 
Information in this chart obtained from NFPA 54, ANSI Z223.1 - 2012 Table 6.2(c)
Table 5 - Pipe-Sizing - Undiluted Propane 
Schedule 40 Metallic Pipe (Black Iron)
Inlet System Pressure: 11 inches W.C.
Allowable Pressure Drop: 0.5 inches W.C.
Specic Gravity : 1.5
(Capacity in cubic feet per hour)
Length Pipe Size (Inches)
½ ¾ 1 1¼ 1½
10 291 608 1150 2350 3520
20 200 418 787 1620 2420
30 160 336 632 1300 1940
40 137 287 541 1110 1660
50 122 255 480 985 1480
60 110 231 434 892 1340
80 101 212 400 821 1230
100 94 197 372 763 1140
125 89 185 349 716 1070
150 84 175 330 677 1010
Information in this chart obtained from NFPA 54, ANSI Z223.1 - 2012 Table 6.3(d)
Table 2 - Pipe-Sizing - Natural Gas 
Schedule 40 Metallic Pipe (Black Iron)
Inlet System Pressure: Less than 2 PSI (55 inches W.C.)
Allowable Pressure Drop: 0.3 inches W.C.
Specic Gravity : 0.60
(Capacity in cubic feet per hour)
Length Pipe Size (Inches)
½ ¾ 1 1¼ 1½
10 131 273 514 1,060 1,580
20 90 188 355 726 1,090
30 72 151 284 583 873
40 62 129 243 499 747
50 55 114 215 442 662
60 50 104 195 400 600
70 46 95 179 368 552
80 42 89 167 343 514
90 40 83 157 322 482
100 38 79 148 304 455
Information in this chart obtained from NFPA 54, ANSI Z223.1 - 2012 Table 6.2(a)
Final Considerations
If this water heater is replacing an existing water heater, 
it is important to verify the capacity of the gas system. 
Check the capacity of the meter/regulator, and verify 
the pipe lengths and sizes.
An improperly sized gas system will cause operational 
issues with this water heater. Other appliances on the 
gas system may be affected as well. 
Flexible Gas Connectors may be used however the 
BTU capacity of the connector must be checked. Each 
connector has a capacity label on it, verify that the 
connector has a BTU capacity greater than that of the 
water heater. An undersized flexible gas connector will 
cause operational issues with this water heater.
Half-inch gas lines are permissible provided the gas 
system meets certain requirements. First, the gas 
pressure on the system must be 8.0 inch W.C. or 
greater. Second the capacity of the pipe as outlined in 
Table 4 is followed. If the existing pipes are too small 
it could cause a pressure drop greater than 3.0 inch 
W.C. and will cause operational issues with this water 
heater as well as other gas appliances on the system.
This is an example, in US, refer to current National Fuel 
Gas Code, NFPA 54 for correct pipe sizing chart, and 
in Canada, refer to current Natural Gas and Propane 
Installation Code CAN/CSA B149.1.