Instructions / Assembly
42
Venting for Direct-Vent Water Heater (cont.)
Horizontal Vent Installation (cont.)
Using a thick bead of high temperature silicone, 
seal the overlapping area of the outer 5-in. (12.7-
cm) pipe.
Attach required vent sections between the water 
heater collar and the horizontal vent termination.
Typical Horizontal Termination with 
1/4 In. Per Foot of DOWNWARD Slope
!
CAUTION:
The condensate collector must be used in 
horizontal terminations if vertical rise in the vent 
system exceeds 2 feet (610 mm).*
NOTICES:
•   Maintain the proper clearance between the 
vent pipe and combustible or noncombustible 
materials as described on page 29.
•   A zero clearance of 0 in. (0 cm) is allowed 
between the air intake pipes and combustible 
material.
•   Use proper support for the vent and air intake 
pipes as described on page 34.
•   Support method used should isolate the 
vent pipe from floor joists or other structural 
members. This helps prevent transmission of 
noise and vibration.
•   DO NOT support, pin, or secure the venting 
system in a way that restricts the normal 
thermal expansion and contraction of the 
chosen venting material.
3
Vent Pipe Wall Plate
Inspection
Access Panel
(Optional)
 Inspection
 Access Panel
 (Optional)
Ceiling Fire
 Stop
2' max.*
(610 mm)
1/4" Per Foot Downward Slope
90˚
Elbow
INSTALLATION INSTRUCTIONS
Venting










