Specifications

December 2008 Page B–7
Appendix B — Troubleshooting
No NOVRAM Error CLEARED
Returned to normal
YesOut of Sync Alarm XCVR1-1
Remote synchronizing signal not received by transceiver 1-1
No Out of Sync Alarm XCVR1-1 CLEARED
Returned to normal
YesOut of Sync Alarm XCVR1-2
Remote synchronizing signal not received by transceiver 1-2
No Out of Sync Alarm XCVR1-2 CLEARED
Returned to normal
YesOut of Sync Alarm XCVR2-1
Remote synchronizing signal not received by transceiver 2-1
No Out of Sync Alarm XCVR2-1 CLEARED
Returned to normal
YesOut of Sync
Alarm XCVR2-2
Remote synchronizing signal not received by transceiver 2-2
No Out of Sync Alarm XCVR2-2 CLEARED
Returned to normal
Information Output 1 Active CLEARED
Returned to normal
Information Output 1
Active
PRI module channel #1 receiving trip from remote PRI
Information Output 2 Active CLEARED
Returned to normal
Information Output 2
Active
PRI module channel #2 receiving trip from remote PRI
Information Output 3 Active CLEARED
Returned to normal
Information Output 3 Active
PRI module channel #3 receiving trip from remote PRI
Information Output 4 Active CLEARED
Returned to normal
Information Output 4 Active
PRI module channel #4 receiving trip from remote PRI
Yes PRI firmware incompatible with settings
PRI firmware version not compatable with hardware (eg. Version 19)
Yes Programmed Setup Mismatch
PRI or HCB module has different settings than Maint. Module
Yes Real
Time Clock Error
When Maint. Module starts the real time clock and the seconds do not count
No Real Time Clock Error CLEARED
Returned to normal
Information Remote Address Programming mismatch
PRI module receiving incorrect remote address
Information Settings Mismatch
PRI module settings differ from those stored by Maint. Module
ALARM, EVENT TEXT,CONT’D
CONCERN? EXPLANATION OF EVENT