Specifications

Page 19–6
FOCUS System Manual
2. Unlock the FOCUS chassis.
If the chassis is locked, execute the “Unlock
Configuration” command on the FCS Setup
menu or click on the “Unlock FOCUS
Chassis” speed button .
This puts the chassis — and the PLD module
— into a configurable state.
3. Insert the PLD Module into the FOCUS
chassis.
Carefully insert the PLD module into the top
and bottom grooves of any open slot on the
FOCUS chassis. Slide it all the way in until it
is well seated in the slot. Lock it into place
using the black inject/eject lever on the front
of the module.
When you first insert the PLD module, the
red/green status LED is red. If the module is
functional, the status LED turns green within
20 seconds. If the module is non-functional,
the status LED stays red, even after 20
seconds have elapsed.
RTU PLD
25-pin 9-pin
“D” Signal Direction “D”
2 TX data > 3
3RX data < 2
4 Request to > 7
Send (RTS)
7 Signal GND 5
8 Data < 6
Carrier
Detect
(DCD
Table 19–2. Pin Assignments for Landis & Gyr
RTUs (TG 0510, TG 5100, TG 5200, TG 5300, TG
5500, TG 5700) to FOCUS PLD.
Master PLD
25-pin 9-pin
“D” Signal Direction “D”
2 TX data < 3
3RX data > 2
7 Signal GND 5
Table 19–3. Pin Assignments for
VALMET Master to FOCUS PLD.
RTU PLD
25-pin 9-pin
“D” Signal Direction “D”
2 TX data > 3
3RX data < 2
4 Request to > 7
Send (RTS)
5 Clear to < 8
Send (CTS)
7 Signal GND 5
Table 19–5. Pin Assignments for
VALMET Cam Dac RTU to FOCUS PLD.
RTU PLD
25-pin 9-pin
“D” Signal Direction “D”
2RX data < 2
3 TX data > 3
4 Clear to < 8
Send (CTS)
5 Request to > 7
Send (RTS)
7 Signal GND 5
Table 19–4. Pin Assignments for
VALMET Micro1/1E RTU to FOCUS PLD.