Specifications

December 2008 Page 14–15
Chapter 14. Protective Relay Interface (PRI/PRS) Module
14
Table 14–5. Protective Relay Interface (PRI/PRS) Alarm Events
Yes PRI firmware incompatible with settings
PRI firmware version not compatable with hardware (eg. Version 19)
No Address mismatch channel A
CLEARED
Returned to normal
No In Block CLEARED
Returned to normal
Yes, if frequent F
AILED to Send Timestamp
MV4 did not receive event timestamp from HCB or PRI module
Yes Programmed Setup Mismatch
PRI or HCB module has different settings than MM
Yes In Block
PRI module channel not communicating with remote PRI
Information Local Address Programming mismatch
MV4 stored PRI settings disagree with module loaded local address
Information Remote Address Programming mismatch
PRI module receiving incorrect remote address
Information Address mismatch channel
A; Received addr: %d
Redundant Path PRI receiving incorrect remote address on pri. channel A; %d = actual
addr. received
Information Address mismatch channel B; Received addr: %d
Redundant Path PRI receiving incorrect remote addr. on redundant path channel B; %d
= actual addr. received
Information Settings Mismatch
PRI module settings differ from those stored by MM
Information Module Reprogrammed
PRI or HCB module reprogrammed at time of module startup
Information Module Resetting
Channel module restarting
Information Programming Failure
PRI or HCB module was not successfully programmed by MM
Information Input 1 Key CLEARED
Returned to normal
Information Input 1 Keyed
PRI module input #1 asserted
Information Input 2 Key CLEARED
Returned to normal
Information Input 2 Keyed
PRI module input #2 asserted
Information Input 3 Key CLEARED
Returned to normal
Information Input 3 Keyed
PRI module input #3 asserted
Information Input 4 Key CLEARED
Returned to normal
ALARM, EVENT TEXT
,
CONCERN? EXPLANATION OF EVENT