Run the connector wire up or along the wall or surface. Apply the adhesive pad that was supplied to the back
side of the tag. Remove the release liner and press firmly to mount the tag to the wall or use screws to mount
the tag using the screw mount bezel.
If mounting the tag in an area where it could potentially be bumped or snagged, you may want to use a strain
relief method to position the sensor connector wire in such as way that if snagged, the wire will not be ripped
from the tag.
Please note that the tag must be mounted in such a way where it will have an unobstructed proximity to the
reader to ensure a correct detection beacon. For example, if mounting the sensor film under a raised floor, the
tag will most likely need to be mounted above the raised floor in order for beacons to be detected.
The R135 Fluid Sensor is designed for detecting fluid in areas where fluid is not a normal occurrence. The sensor
should not be used in any application where the sensor is normally in a wet state and is required to a report dry
state as an alert condition. After the Fluid sensor has become wet it should be dried and retested for proper
operation.