Submittal
Reznor X Series Duct Furnaces are designed to provide 80% thermal efciency for indoor application with
gravity venting. They are certied for use with natural or propane gas, as specied, in sizes from 75,000
through 400,000 BTUH input. These models are used as heating components in heating, heating/cooling, or
makeup air systems and require a separate blower system for air delivery. The furnace has a Reznor Thermo-
core
®
aluminized steel heat exchanger with venturi-design tubes. The die-formed burners are of aluminized
steel and include ared ports with a stainless steel insert.
The Model X furnace is approved for a temperature rise of 50°F to 90°F and includes “nger-bafes” for proper
air distribution at these lower air volumes. Removing the nger-bafes increases the air ow. These eld con-
verted units are approved for a temperature rise of 20°F to 75°F.
Standard features include a spark ignition pilot and a single-stage, 24-volt gas valve. Model X units are wired
for eld connection to a remote 24-volt thermostat for automatic operation. Each unit is provided with all re-
quired limit and safety controls, including a blocked vent shut-off system.
● Orices for natural gas
● Aluminized steel heat exchanger
● Aluminized steel burners with stainless steel insert
● 120-volt supply voltage
● 24 volt control voltage transformer
● High limit safety cutout
● Single-stage combination gas valve (see note 1)
● Side access for burners and controls (left side facing air stream)
● Horizontal or vertical ue discharge
● Spark-ignited pilot
● Fan control
● Terminal blocks for connecting eld wiring
● Blocked vent shut-off system
● Unit equipped for propane gas
● E-3 (409) stainless steel heat exchanger (see note 2)
● E-3 (409) stainless steel burners (see note 2)
● E-3 (409) stainless steel drip pan (see note 2)
● Gas Controls
♦ Spark-ignited intermittent safety pilot with electronic ame supervision
♦ Spark-ignited intermittent safety pilot with electronic ame supervision and timed lockout
♦ Two-stage controls
♦ Electronic modulation - 50%-100% ring rate
● Burner air shutters (required on units equipped with propane gas)
● 208/230/460-volt alternate supply voltage
● Right side controls (facing airstream)
DESCRIPTION
STANDARD FEATURES
OPTIONAL FEATURES -
FACTORY INSTALLED
NOTES:
1. Regulated combinationredundant gasvalve consistsof combinationpilot solenoid valve,electric gasvalve, pilotlter,pressure
regulator,pilotshut-off,andmanualshut-off,allinonebody.Gassupplypressuremustnotexceed0.5PSI(8oz.-14”w.c.).Minimum
inletpressurefornaturalgasis5”w.c.Minimuminletpressureforpropanegasis11”w.c.
2. Forairinlettemperaturesbelow40°Fortemperatureriselessthan40°F,anoptionalstainlesssteelheatexchangerisrecommended.
3. See temperature rise and pressure drop tables.
4. Blowermustbeplacedonenteringsideoffurnace.
5. Approvedforinstallationdownstreamofanairconditioningcoil(optionaldrainange,stainlesssteelheatexchanger,andstainless
steelburnersarerecommended).
6. Not approved for residential use.
MODEL X
INDOOR, GAS-FIRED, GRAVITY-VENTED DUCT FURNACE FOR COMMERCIAL/
INDUSTRIAL USE
CGA 2.6
ANSI Z83.8
Form RZ-C-DH Page 8
Page Number _______ of ______