Brochure

www.ReznorHVAC.com
Hydronic Heating
Increased Air Throw Capacity
The Air Flow Induction Optimizer increases the throw for Reznor Models WS.
This increased ow results in energy savings and better environmental control.
The unique shape of the deecting louvers which create layers of hot air at the
unit outlet. The space created between layers causes air around the front of the
unit to be drawn into the air stream and mixed with the heated air. The result is
a signicant increase in the air throw.
Model WS 18/24 23/33 44/62 60/85 78/110 96/120 140/175 190/238 300/350
Maximum Heating
Capacity (MBH)
Fan
Speed
Low 18 23 44 60 78 96 140 190 300
High 24 33 62 85 110 120 175 238 350
Maximum Leaving
Air Temperature
°F
Low 121° 124° 132° 129° 125° 134° 134° 140° 133°
High 115° 121° 126° 123° 121° 131° 130° 137° 128°
Noise Level at 16-1/2 ft
(5m) - dB(A)
Low 45 46 49 54 57 47 49 52 61
High 52 54 58 63 65 52 55 60 67
Approximate Air
Volume
CFM
Low 270 330 560 800 1,100 1,200 1,750 2,200 3,800
High 400 500 860 1,250 1,650 1,550 2,300 2,850 4,750
Electrical Power 115/1/60 - 240/1/50 (50 Hz available on request)
Working Pressure Hot Water - 150 psi; Steam - 145 psi
If you need hydronic (steam or hot water) heating, Reznor
Model WS is the heater of choice.
Versatile
» Each unit can be mounted for horizontal or vertical
(down) air delivery
» Units can be selected to operate at 60 Hz or 50 Hz
» Accurate size selection can be determined by using
Reznor selection software program
Dependable - The standard totally enclosed motors
have internal overload protection
Adjustable - Every motor can be eld set for high
speed/low speed
» High speed for expanded oor coverage
» Low speed for higher temperature rise
Sturdy - The heat exchanger of every unit is pressure
tested at the factory
Quiet - Fans are mounted with vibration isolation for
smooth operation
TECHNICAL DATA
Model WS